CFM Corporation UVDR36C 사용자 설명서

다운로드
페이지 16
4
UVDR Series Unvented Gas Fireplaces
20007469
Locating the Fireplace
Figure 2 shows some of the many ways your fireplace 
may be installed. Consider the traffic pattern in your 
room and the location of doors and windows. Moving 
air from ceiling fans, open doors and hot air grilles may 
cause the flames to soot. If a disturbance is found that 
effects the flames, it must be eliminated by turning off 
the ceiling fan, closing the door or closing or moving 
the hot air register. A corner location may be best where 
space is limited.
Your fireplace weighs no more than some of your fine 
furniture. If the fireplace is located near a load bear-
ing wall, additional supports to the foundation will not 
be necessary. HEAVY FACINGS SUCH AS BRICK, 
STONE, ETC., MAY REQUIRE ADDITIONAL FOUNDA-
TION SUPPORT.
ALTHOUGH THIS UNIT MAY BE INSTALLED ON 
COMBUSTIBLE SURFACES, IT MUST NOT BE IN-
STALLED ON CARPET OR VINYL.
Room Divider
Partial Room
Projection
Full Room
Projection
Flush
Corner
T224
place fireplace
2/04
T224
Fig. 2  Locating the fireplace.
Gas Line
The gas line must be installed before framing in the fire-
place by a licensed gas line installer.
Drafts
Do not locate the fireplace in high traffic areas or areas 
exposed to high drafts and winds. Locate the fireplace 
away from furniture and draperies.
Fireplace Clearances
The fireplace may be placed directly on a combustible 
floor, against a combustible wall at marked clearances 
or on a raised wooden platform.
If the fireplace is to be installed on a raised wooden 
platform, the platform must be a continuous level sur-
face. The fireplace must be secured in place so it can-
not shift positions. The nailing flanges on the sides of 
the firebox make securing it to the framing easy. They 
were designed to allow the installation of 1/2” wallboard 
or plywood flush with the face of the fireplace.
Only the header (Fig. 1) may rest on the standoffs on 
top of the firebox.
When the fireplace is installed over carpeting, vinyl, tile 
or any combustible material other than wood flooring, it 
must be installed on a metal or wood panel extending 
its full width and depth. Alternatively, the carpeting, vinyl 
tile, etc., may be removed from beneath the fireplace 
before installing. COMBUSTIBLE MATERIALS MUST 
NOT BE INSTALLED OVER OR TOUCH ANY BLACK 
PAINTED SURFACE. DO NOT BLOCK HEAT CIRCU-
LATING AIR OUTLETS. DOING SO MAY RESULT IN 
POTENTIAL FIRE HAZARD.
Clearances
To ensure a safe installation the following instructions 
must be carefully observed.
1.  Sidewall Clearances:  Clearances from the side of 
the fireplace opening to any combustible wall should 
not be less than 5”. (Fig. 3a)
2.  Ceiling Clearances:  The ceiling height should not 
be less than 42” from the top of the fireplace open-
ing.
3.  Mantel Clearances:
a.  If the fireplace has no mantelpiece, then the heat 
resistant material must extend upwards a dis-
tance of at least 9¹⁄₂" from the fireplace opening. 
A mantel projection must be a minimum of 24” 
above the top fireplace opening if a canopy is not 
installed. (Fig. 3b)
b.  Noncombustible materials used in this installation 
such as slate, marble, tile, etc. must be at least  
1/2" thick. Do not install a combustible material 
behind sheet metal. Failure to use noncombus-
tible materials above the opening as specified 
in these instructions may cause damage to the 
materials used and create a fire hazard.
c.  A heat reducing canopy is shipped with the 
fireplace. Use of this canopy is optional in order 
to reduce mantel heights as shown in Figure 3d.  
If the canopy is installed, a combustible mantel 
piece may project 2" from the wall at 6¹⁄₂" above 
the fireplace opening. A 6" mantel projection at 
13" above the fireplace opening and a 10" projec-
tion at 22" above the opening. (Fig. 3a and 3d)  
  To install the optional canopy, remove the four (4) 
screws supplied with a Phillips screwdriver. Two (2) 
Installation Instructions