INSTALLATION
CONNECTING TO GAS SUPPLY
       WARNING:  A  qualified
service  person  must  connect
heater  to  gas  supply. Follow  all
local  codes.
           WARNING:  This  appliance
requires  a  3/8
"
  NPT  (National
Pipe  Thread)  inlet  connection
to  the  pressure  regulator.
          CAUTION:  Never  connect
h e a t e r     d i r e c t l y     t o       t h e
propane/LP  supply. This  heater
requires  an  external  regulator
( n o t     s u p p l i e d ) .   I n s t a l l     t h e
external  regulator  between  the
heater  and  propane/LP  supply.
*A  CSA/AGA  design-certified  equipment  shutoff  valve  with  1/8
"
  NPT  tap  is
an  acceptable  alternative  to  test  gauge  connection.  Purchase the  optional
C S A / A G A    d e s i g n - c e r t i f i e d     e q u i p m e n t     s h u t o f f     v a l v e     f r o m
your  dealer.  See  Accessories,  page 17.
IMPORTANT:  Install  an  equipment
shutoff  valve  in  an  accessible
location. The  equipment  shutoff
valve   is  for  turning  on  or  shutting
off  the  gas  to  the  appliance.
Install  sediment  trap  in  supply  line
as  shown  in  Figure 14.  Locate
sediment  trap  where  it  is  within
r e a c h       f o r     c l e a n i n g .     L o c a t e
sediment    trap   where   trapped
matter  is  not  likely  to  freeze.  A
sediment   trap  traps  moisture  and
contaminants.  This   keeps  them
from  going  into  heater  controls.  If
sediment  trap  is  not  installed    or  is
i n s t a l l e d     w r o n g ,     h e a t e r     m a y
not  run  properly.
IMPORTANT:    Hold   pressure
r e g u l a t o r     w i t h     w r e n c h     w h e n
connecting it to gas piping and/or
fittings.
           CAUTION:   Use   pipe   joint
sealant  that  is  resistant  to
liquid  petroleum (LP)  gas.
Figure 14 -Gas  Connection
The   installer   must   supply   an
external  regulator. The  external
regulator  will  reduce  incoming  gas
p r e s s u r e .   Yo u     m u s t     r e d u c e
incoming  gas  pressure  to  between
11  and  14  inches  of  water. If  you
do  not  reduce  incoming  gas
pressure, heater  regulator  damage
c o u l d     o c c u r .   I n s t a l l     e x t e r n a l
regulator  with  the  vent   pointing
down  as  shown  in  Figure  13.
Pointing  the  vent  down  protects  it
from  freezing  rain  or  sleet.
Figure 13 - External  Regulator  with
                  Vent  Pointing  Down
       CAUTION:  Use  only  new,
b l a c k   i r o n     o r   s t e e l     p i p e .
Internally-tinned  copper  tubing
may  be  used  in  certain  areas.
Check   your  local  codes.  Use pipe
of  large  enough   diameter to
allow  proper  gas  volume  to heater.
I f       p i p e       i s       t o o       s m a l l ,
undue  loss  of pressure  will occur.
Typical Inlet Pipe Diameters
All models up to 20,000 BTU’s use
3/8’’ or greater pipe;
All models 25,000 BTU’s and higher,
use 1/2” or greater pipe.
Installation   must   include  an
equipment   shutoff   valve,   union,
and  plugged  1/8
"
 NPT  tap.  Locate
NPT tap within  reach  for  test  gauge
hook   up.   NPT  tap  must  be
upstream  from  heater  (see  Figure
14).
Apply  pipe  joint  sealant  lightly  to
male  threads.  This  will  prevent
excess  sealant  from  going  into
pipe.  Excess  sealant  in  pipe  could
result  in  clogged  heater  valves.
From External
LP Gas Regulator