Operator’s Manual
Preparation
VENTILATION
   WARNING: FOLLOW THE MINIMUM FRESH, OUTSIDE  
    AIR VENTILATION REQUIREMENTS. IF PROPER  
    FRESH,  OUTSIDE  AIR  VENTILATION  IS  NOT  
    PROVIDED,  CARBON  MONOXIDE  POISONING  
    CAN OCCUR. PROVIDE PROPER FRESH, OUTSIDE  
    AIR VENTILATION BEFORE RUNNING HEATER.
Provide a fresh air opening of at least three square feet for 
each 100,000 Btu/Hr rating. Provide extra fresh air if more 
heaters are being used.
PROPANE SUPPLY
Propane / L.P. gas and Propane / L.P.  tank(s) are to be 
furnished by the user.
Use  this  heater  only  with  a  propane  vapor  withdrawal 
supply system. See Chapter 5 of the Standard for Storage 
and Handling of Liquefied Petroleum Gas, ANSI/NFPA 58 
and the Propane Installation Code CAN/CGA B149.2. Your 
local library or fire department will have this booklet.
The  amount  of  Propane  /  L.P.  gas  ready  for  use  from 
Propane / L.P. tanks varies. Two factors decide this amount: 
1. The amount of Propane / L.P. gas in tank(s)
2. The temperature of tank(s)
The chart below shows the number of 100 pound (45 kg) 
tanks needed to run this heater. Smaller tanks can be used 
for limited run times but it is recommended to use larger 
tanks for optimum performance.
Less gas is vaporized at lower temperatures. You may need 
two or more 100 pound (45 kg) tanks or one larger tank in 
colder weather. Your local Propane / L.P. gas dealer will 
help you select the proper supply system. The minimum 
surrounding air temperature rating for each heater is 
-20° F (-29° C).
Temperature at Tank
# of 100 lbs. Tanks
32°F (0°C) to 20°F (-6.7°C)
2
20°F (-6.7°C) to -10°F (-23.3°C)
3
Below -10°F (-23.3°C)
(Use larger tank)