Point Database 
Siemens Building Technologies, Inc. 
 
19 
Description Address  Application 
Description 
RM STPT MlN 
11 
2583, 2584 
Minimum temperature setpoint in degrees that the controller 
can use from the setpoint dial. This overrides any 
temperature setpoint from the setpoint dial that falls below 
this minimum. 
Valid entry range: 48° to 95°F (9° to 35°C) 
RM STPT MAX 
12 
2583, 2584 
Maximum temperature setpoint in degrees that the controller 
can use from the setpoint dial. This overrides any 
temperature setpoint from the setpoint dial that raises above 
this maximum. 
Valid entry range: 48° to 95°F (9° to 35°C) 
RM STPT DIAL 
{13} 
2583, 2584, 2590 
Temperature setpoint in degrees from the room temperature 
sensor (not available on all temperature sensor models). 
This setpoint will be used for control in day mode (heating or 
cooling) when enabled by STPT DIAL (Point 14). 
Valid entry range: 48° to 95°F (9° to 35°C) 
STPT DIAL 
14 
2583, 2584 
YES indicates that there is a room setpoint dial on the room 
temperature sensor and must be used as the temperature 
setpoint for control in day/occupied mode. NO indicates that 
the appropriate preset setpoint will be used as the 
temperature setpoint for control in day/occupied heating or 
cooling mode. 
Valid input: YES or NO 
AUX TEMP 
{15} 
2590 
Actual reading from a 10K Ω thermistor connected to the 
controller's AI 5 input. When a thermistor is connected at  
Al 5, DI 5 is not available. See DI 5. The physical input can 
not be used for both analog and digital input at the same 
time. 
MA TEMP 
{15} 
2583, 2584 
Actual reading from a 10K Ω thermistor connected to the 
controller's Al 5 input. When a thermistor is connected at  
Al 5, DI 5 is not available. See DI 5. The physical input can 
not be used for both analog and digital input at the same 
time. 
CMP2 ON 
16 
2583 
Value, in percent, that the active temperature control loop 
output must exceed for compressor 2 to turn ON. Actual 
turn on is subject to the CMP2 MlN OFF time being expired. 
HTG CMP2 ON 
16 
2584 
Value, in percent, that the heating control loop output must 
exceed for compressor 2 to turn ON. Actual turn on is 
subject to the CMP2 MlN OFF time being expired. 
CMP2 OFF 
17 
2583 
Value, in percent, that the active temperature control loop 
output must go below for compressor 2 to turn OFF. Actual 
turn off is subject to the CMP2 MlN ON  time being expired. 
HTG CMP2 OFF 
17 
2584 
Value, in percent, that the heating control loop output must 
go below for compressor 2 to turn OFF. Actual turn off is 
subject to the CMP2 MlN ON time being expired. 
WALL SWITCH 
18 
2583, 2584, 2590 
YES indicates that the controller is to monitor the status of a 
wall switch that is connected to Dl 2. NO indicates that the 
controller will not monitor the status of a wall switch, even if 
one is connected. 
Valid input: YES or NO