Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual 
20  
Siemens Building Technologies, Inc. 
Description Address  Application 
Description 
Dl OVRD SW 
{19} 
2583, 2584, 2590 
Actual indication of the status of the override switch (not 
physically available on all temperature sensor models) at the 
room temperature sensor. ON indicates that the switch is 
being pressed. OFF indicates that the switch is released. 
Valid input: ON or OFF 
OVRD TIME 
20 
2583, 2584 
Amount of time in hours that the controller will operate in 
day/occupied mode when the override switch is pressed 
while the controller is in night/ unoccupied mode. 
NGT OVRD 
{21} 
2583, 2584 
Indicates the mode that the controller is operating in with 
respect to the override switch. NIGHT indicates that the 
switch has not been pressed and the override timer is not 
active. DAY indicates that the switch has been pressed and 
the override timer is active. The controller then uses a day 
mode temperature setpoint. This point is only in effect when 
DAY.NGT indicates night mode. 
RMTMP OFFSET 
22 
All 
 
Compensates for deviations between the value of ROOM 
TEMP and the actual room temperature. This corrected 
value is displayed in CTL TEMP. 
RMTMP OFFSET + ROOM TEMP = CTL TEMP 
FREE CLG 
{23} 
2583, 2584 
Point commanded by the field panel PPCL to enable or 
disable mixed air control (free cooling). 
DI 2 
{24} 
2583, 2584, 2590 
Actual status of a contact connected to the controller at Dl 2. 
ON indicates that the contact is closed; OFF indicates that 
the contact is open. If a wall switch is used, it is connected 
to DI 2. See WALL SWITCH. 
DI 5 
{25} 
2583, 2584, 2590 
Actual status of a contact connected to the controller at  
Al 5/Dl 5. ON indicates that the contact is closed; OFF 
indicates that the contact is open. When a contact is 
connected at Dl 5, Al 5 is not available. See Point number 
15The physical input can not be used for both analog and 
digital input at the same time. 
DI 6 
{26} 
2583, 2584, 2590 
Actual status of a contact connected to the controller. ON 
indicates that the contact is closed; OFF indicates that the 
contact is open. Application 2583/2584: DI 6 can be used to 
monitor an input that changes state when the heat pump is 
in alarm. DI 6 can be unbundled to send alarm information 
to the field panel for centralized alarm monitoring. 
CMP2 MlN OFF 
27 
2583 
Minimum time, in minutes, that compressor 2 will remain 
OFF before turning ON. 
HTG2 MlN OFF 
27 
2584 
Minimum time, in minutes, that heating compressor 2 will 
remain OFF before turning ON. 
CMP2 MlN ON 
28 
2583 
Minimum time, in minutes, that compressor 2 will remain ON 
before turning OFF. 
HTG2 MlN ON 
28 
2584 
Minimum time, in minutes, that heating compressor 2 will 
remain ON before turning OFF.