Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual 
22  
Siemens Building Technologies, Inc. 
Description Address  Application 
Description 
DO 1 
{41} 
2583, 2584, 2590 
Digital output 1 controls a 24 Vac load with an ON or OFF 
status. If Motor 1 is enabled, DO 1 is coupled with DO 2 to 
control an actuator. 
DO 2 
{42} 
2583, 2584, 2590 
Digital output 2 controls a 24 Vac load with an ON or OFF 
status. lf Motor 1 is enabled, DO 2 is coupled with DO 1 to 
control an actuator. 
DO 3 
{43} 
2590 
Digital output 3 controls a 24 Vac load with an ON or OFF 
status. lf Motor 2 is enabled, DO 3 is coupled with DO 4 to 
control an actuator. 
ELEC HEAT 
{43} 
2584 
This output controls the contact for the first stage of electric 
heat and has a status of ON or OFF. 
ELEC HEAT 1 
{43} 
2583 
This output controls the contact for the first stage of electric 
heat and has a status of ON or OFF. 
DO 4 
{44} 
2590 
Digital output 4 controls a 24 Vac load with an ON or OFF 
status. lf Motor 2 is enabled, DO 4 is coupled with DO 3 to 
control an actuator. 
HTG CMP 1 
{44} 
2584 
Digital output used to control the heating compressor 1. 
REV VALVE 
{44} 
2583 
Digital output used to control the reversing valve.  
COOL and HEAT status is indicated for the 24 Vac valve or 
relay. The default configuration is energized for HEAT. The 
configuration may be reversed in DO DIR.REV. 
DO 5 
{45} 
2590 
Digital output 5 controls a 24 Vac load with an ON or OFF 
status. lf Motor 3 is enabled, DO 5 is coupled with DO 6 to 
control an actuator. 
COMPRESSOR 1 
{45} 
2583 
Digital output used to control the compressor. ON or OFF 
status is indicated for the 24 Vac relay. 
HTG CMP 2 
{45} 
2584 
Digital output used to control heating compressor 2. ON or 
OFF status is indicated for the 24 Vac relay. 
CLG CMP 1 
{46} 
2584 
Digital output used to control cooling compressor 1. 
DO 6 
{46} 
2590 
Digital output 6 controls a 24 Vac load with an ON or OFF 
status. lf Motor 3 is enabled, DO 6 is coupled with DO 5 to 
control an actuator. 
EHEAT3.CMP2 
{46} 
2583 
Digital output used to control either compressor 2 or the 
third stage of electric heat. 
CLG CMP 2 
{47} 
2584 
Digital output used to control cooling compressor 2. 
DO 7 
{47} 
2590 
Digital output 7 controls a 24 Vac load with an ON or OFF 
status. 
EHEAT2.CMP3 
{47} 
2583 
Digital output used to control either compressor 3 or 2nd 
stage of electric heat. 
DMPR COMD 
{48} 
2583, 2584 
Value to which the damper motor is commanded in percent 
of full travel. 
MTR1 COMD 
{48} 
2590 
Value to which the Motor 1 actuator is commanded in 
percent of full travel.