COOLING CAPACITIES -
4 TON (BCH048)
Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
85
°
F
95
°
F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2000
72
56
4.1
42
36
31
26
-
-
-
53
4.5
40
35
29
24
-
-
-
67
53
4.0
48
47
41
36
30
25
-
51
4.4
46
45
41
35
30
24
-
62
49
4.0
49
49
48
44
38
33
28
46
4.3
46
46
45
41
35
30
24
57
49
3.9
49
49
49
44
38
33
28
46
4.3
46
46
46
41
35
30
24
1800
72
55
4.0
40
35
30
25
-
-
-
53
4.4
38
33
28
23
-
-
-
67
52
4.0
47
44
39
34
29
24
-
51
4.4
44
44
39
34
29
24
-
62
48
3.9
48
48
47
43
38
33
28
47
4.3
47
47
45
40
36
31
26
57
48
3.9
48
48
48
43
38
33
28
45
4.2
45
45
45
40
35
30
25
1600
72
53
4.0
37
33
28
24
-
-
-
52
4.4
36
32
27
23
-
-
-
67
51
4.0
46
42
37
33
28
24
-
50
4.3
44
43
38
34
29
25
-
62
47
3.9
47
47
46
41
37
32
28
45
4.2
45
45
44
40
36
31
27
57
47
3.9
47
47
47
42
38
33
29
44
4.1
44
44
44
40
36
31
27
1400
72
52
4.0
34
30
26
22
-
-
-
49
4.3
33
29
25
21
-
-
-
67
49
3.9
42
38
34
30
26
22
-
47
4.2
42
38
34
30
26
22
-
62
46
3.8
46
45
42
38
34
30
26
43
4.1
43
42
40
36
32
28
24
57
45
3.8
45
45
43
39
35
31
27
42
4.1
42
42
40
36
32
28
24
1200
72
50
3.9
31
27
24
20
-
-
-
47
4.2
29
25
22
18
-
-
-
67
47
3.9
38
35
31
28
24
21
-
45
4.2
37
34
30
27
23
20
-
62
44
3.8
44
42
39
35
32
28
25
40
4.1
40
39
36
32
29
25
22
57
44
3.7
44
43
39
36
32
29
25
40
4.0
40
39
36
32
29
25
22
Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
105
°
F
115
°
F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2000
72
51
4.9
40
35
29
24
-
-
-
49
5.2
39
34
29
23
-
-
-
67
46
4.7
42
42
39
34
28
23
-
41
5.0
40
40
37
32
26
21
-
62
43
4.6
43
43
42
37
32
27
21
40
4.9
40
40
39
34
29
23
18
57
43
4.6
43
43
43
38
32
28
22
40
4.8
40
40
40
34
30
24
19
1800
72
50
4.8
38
33
28
23
-
-
-
47
5.1
37
32
27
22
-
-
-
67
45
4.7
41
41
37
32
27
22
-
40
4.9
37
36
35
30
25
20
-
62
42
4.6
42
42
41
37
32
27
22
39
4.8
39
39
37
34
29
24
19
57
42
4.5
42
42
42
37
33
27
23
38
4.7
38
38
38
33
30
25
20
1600
72
49
4.8
35
31
26
22
-
-
-
46
5.1
34
29
25
20
-
-
-
67
44
4.6
40
40
35
31
26
22
-
39
4.9
36
36
32
28
23
19
-
62
41
4.5
41
41
40
35
32
27
23
37
4.7
37
37
36
33
28
24
19
57
41
4.4
41
41
41
36
32
28
23
37
4.7
37
37
37
34
28
25
20
1400
72
47
4.7
32
28
24
20
-
-
-
44
5.0
31
27
23
19
-
-
-
67
42
4.5
38
36
32
28
24
20
-
37
4.8
36
34
30
26
21
17
-
62
39
4.4
39
38
37
33
28
25
20
36
4.7
36
35
34
30
26
22
18
57
39
4.4
39
39
37
33
29
25
21
36
4.6
36
36
34
31
26
23
19
1200
72
44
4.6
28
25
21
18
-
-
-
42
4.9
28
24
21
17
-
-
-
67
40
4.5
36
32
29
25
22
18
-
36
4.7
34
31
27
24
20
17
-
62
38
4.4
38
36
34
29
27
22
20
35
4.6
35
34
30
28
24
20
17
57
37
4.3
37
37
34
30
27
23
20
35
4.6
35
35
31
29
24
21
18
1
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by
3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2
These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW.
Refer to the Blower Performance Table for the KW of the supply air blower motor.
ALL SENSIBLE CAPACITY
NOMINAL RATING