York 48 사용자 설명서

다운로드
페이지 24
036-21564-002-A-0404
6
Unitary Products Group
COOLING CAPACITIES -
5 TON (BCH060)
Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
85
°
F
95
°
F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2500
72
68
5.7
51
44
38
31
-
-
-
67
6.0
51
45
38
31
-
-
-
67
65
5.6
58
56
50
43
37
30
-
64
5.9
56
56
50
43
37
30
-
62
61
5.6
61
61
59
53
46
39
33
59
5.9
59
59
57
50
44
38
31
57
60
5.5
60
60
59
53
47
40
33
58
5.8
58
58
57
51
44
39
32
2250
72
67
5.6
48
42
36
30
-
-
-
66
5.9
48
42
36
30
-
-
-
67
64
5.6
57
54
48
42
36
30
-
63
5.9
55
54
48
42
35
29
-
62
60
5.5
60
60
57
51
45
39
33
57
5.8
57
57
55
50
44
38
32
57
59
5.5
59
59
58
52
46
40
34
57
5.8
57
57
56
50
45
39
33
2000
72
66
5.6
45
40
34
29
-
-
-
65
5.9
45
40
34
29
-
-
-
67
63
5.5
56
51
45
40
35
29
-
61
5.9
55
51
45
40
34
29
-
62
59
5.4
59
59
55
50
44
39
33
56
5.8
56
56
54
49
44
38
33
57
58
5.4
58
58
57
52
46
41
36
56
5.7
56
56
55
50
44
39
34
1750
72
64
5.5
42
37
32
27
-
-
-
62
5.9
43
38
33
28
-
-
-
67
61
5.5
52
47
42
37
33
28
-
59
5.8
53
48
44
39
34
29
-
62
57
5.4
57
56
51
46
41
37
32
54
5.7
54
54
52
48
43
38
33
57
57
5.4
57
57
53
48
44
39
34
54
5.7
54
54
53
49
43
39
34
1500
72
62
5.5
38
34
30
25
-
-
-
60
5.8
41
36
32
28
-
-
-
67
59
5.5
48
43
39
35
31
26
-
57
5.8
51
46
42
38
34
29
-
62
55
5.4
55
52
47
43
39
35
30
52
5.7
52
52
50
46
42
38
34
57
55
5.3
55
54
49
45
41
37
32
52
5.6
52
52
51
47
42
39
35
Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
105
°
F
115
°
F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2500
72
64
6.0
51
44
38
31
-
-
-
60
6.9
50
43
37
30
-
-
-
67
59
5.9
51
51
49
42
36
29
-
54
6.6
54
53
47
41
34
27
-
62
54
5.9
54
54
51
46
40
33
26
49
6.5
49
49
48
42
35
28
22
57
54
5.8
54
54
52
46
41
33
26
49
6.5
49
49
49
43
35
28
23
2250
72
63
5.9
48
42
36
30
-
-
-
60
6.8
47
41
35
29
-
-
-
67
58
5.9
51
51
46
40
34
28
-
54
6.6
47
47
45
39
32
26
-
62
53
5.8
53
53
52
46
40
34
28
49
6.5
49
49
47
42
36
30
24
57
53
5.8
53
53
52
46
41
35
27
49
6.4
49
49
48
43
37
31
25
2000
72
62
5.9
45
39
34
28
-
-
-
59
6.8
44
38
33
27
-
-
-
67
57
5.9
51
49
44
38
33
27
-
53
6.5
45
45
42
36
31
26
-
62
52
5.8
52
52
51
46
40
35
30
48
6.4
48
48
46
42
36
31
25
57
52
5.7
52
52
51
46
40
36
31
47
6.4
47
47
46
43
36
32
25
1750
72
60
5.9
41
37
32
27
-
-
-
56
6.7
40
35
30
25
-
-
-
67
55
5.8
48
46
41
36
31
26
-
51
6.5
43
43
38
33
29
24
-
62
50
5.7
50
50
48
43
39
34
29
46
6.4
46
46
43
38
33
28
24
57
50
5.7
50
50
48
43
39
34
30
45
6.3
45
45
43
38
33
28
25
1500
72
57
5.8
38
34
30
25
-
-
-
53
6.6
36
31
27
23
-
-
-
67
53
5.8
47
43
38
34
30
26
-
48
6.4
41
39
35
30
26
22
-
62
48
5.7
48
48
45
41
37
32
28
44
6.3
44
44
39
35
30
26
22
57
48
5.6
48
48
45
41
38
32
28
43
6.2
43
43
40
36
30
26
23
1
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by
3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2
These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW.
Refer to the Blower Performance Table for the KW of the supply air blower motor.
ALL SENSIBLE CAPACITY
NOMINAL RATING