Lochinvar 2 사용자 설명서

다운로드
페이지 60
        
Installation & Operation Manual
Low voltage connections 
1.  Route all low voltage wires through the knockouts in the 
rear of the boiler,  as shown in FIG. 7-2.
2.  Connect low voltage wiring to low voltage connection 
board as shown in FIG. 7-3 on page 38 of this manual and 
the boiler wiring diagram.
LINE VOLTAGE
J-BOX
LOW VOLTAGE
J-BOX
LOW VOLTAGE
WIRING KNOCKOUTS
LINE VOLTAGE
WIRING KNOCKOUTS
Figure 7-2 Routing Field Wiring
7  
Field wiring     
Enable
1.  Connect the room thermostat or boiler enable contacts 
(isolated contact only) to terminals 7 and 8, as shown in  
FIG. 7-3.
2.  If a thermostat is used, install the thermostat on the inside 
wall away from influences of drafts, hot or cold water 
pipes, lighting fixtures, television, sunlight, or fireplaces.
3.  Thermostat anticipator (if applicable):
 
a. 
If connected directly to boiler, set for 0.1 amps.
 
b.  If connected to relays or other devices, set to match 
  
total electrical power requirements of connected 
  
devices.  See device manufacturers’ specifications 
  
and thermostat instructions for details.
Outdoor temperature sensor
1.  Connect the outdoor temperature sensor (FIG. 7-3) to 
the Outdoor Sensor terminals on the connection board to 
enable outdoor reset operation of the Crest.  
2.  Mount the sensor on an exterior wall, shielded from direct 
sunlight or flow of heat or cooling from other sources.
3.  Route sensor wires through a knockout at the rear of the 
boiler (see FIG. 7-2).
Variable speed system pump
If a variable speed pump is used in the primary loop, and 
a 0-10V signal is available from the pump speed control, 
this signal can be used by the SMART TOUCH control to 
anticipate changes in the building heat load.  By connecting 
this 0 - 10V signal to the 0 - 10V SYS PUMP IN terminals, the 
boiler (or cascade) can modulate up and down as the primary 
flow increases and decreases.
ModBus
The RS-485 ModBus cable is connected to the ModBus 
terminals.  Use shielded, 2-wire twisted pair cable.  If desired, 
the shield can be connected to ground by installing a jumper 
wire between terminals 1 and 3 on connector X5 on the 
ModBus interface module.
Hot Water Generator (HWG) 
thermostat
1.  Connect the HWG tank thermostat to the Tank 
Thermostat  terminals  on  the  connection  board           
(FIG. 7-3).
Hot Water Generator (HWG) tank 
sensor
1.  By installing a HWG tank sensor, the SMART TOUCH 
control can perform the tank thermostat function.  The 
SMART TOUCH control automatically detects the 
presence of this sensor, and generates a HWG call for heat 
when the tank temperature drops 6°F (3°C) below the 
tank set point, and finishes the call for heat when the tank 
temperature reaches the tank set point.
2.  A TST20015 sensor MUST be used with any indirect tank.  
Failure to use the correct sensor will result in the tank 
temperature being either above or below the set point.  
Connect the correct sensor to the Tank Sensor terminals 
(see FIG. 7-3).
Louver relay
If louvers need to operate before the boiler fires, they can be 
controlled by this output.  Connect these terminals to a 24V 
relay coil, which is wired to operate the louvers (FIG. 7-3).
Louver proving switch
Louvers are used to provide combustion air for the room air 
option.  A louver proving switch should be connected to the 
appropriate terminals and are verified prior to operation (see 
FIG. 7-3).
Boiler pump speed output
This 0 - 10V output is available to control the speed of a 
variable speed boiler pump.  The SMART TOUCH control will 
vary the speed of this pump in order to maintain a minimum 
T (set by the installer, see the Crest Service Manual) across 
the heat exchanger, as well as prevent high limit lockouts when 
the flow in the primary loop is extremely low.  Connect this 
output to the 0 - 10V input on the boiler pump speed control.
Rate output
This output provides a 0 - 10V signal that is proportional to 
the firing rate of the boiler.  This may be used by a BMS system 
to monitor the actual rate of the boiler.
36
 NOTICE
A system supply sensor must be installed 
for this feature to work.