Lochinvar 5 사용자 설명서

다운로드
페이지 68
           
Installation & Operation Manual
It is required that near boiler piping systems 
utilize Primary/Secondary configurations as 
shown in FIG.’s 5-5 and 5-6 only.  The use of 
other near boiler piping configurations could 
result in improper building and system flow 
rates leading to inadvertent boiler high limit 
shutdowns and poor system performance.
Near boiler piping components
1. Boiler 
piping:
 
Boiler system piping MUST be sized per the pipe 
 
requirements listed in Table 5A.  Reducing the pipe size 
 
can restrict the flow rate through the boiler, causing 
 
inadvertent high limit shutdowns and poor system 
 
performance.   
2.  Boiler circulating pump:
 
Field supplied.  The boiler circulating pump MUST be 
 
sized to meet the specified minimum flow requirements 
 
listed in FIG. 5-4.
3.  Hot Water Generator circulating pump:
 
Field supplied.  The pump MUST be sized to meet 
 
the specified minimum flow requirements listed in 
 
 
 
FIG. 5-4.  Consult the indirect boiler operating 
 
guide to determine flow characteristics for the selected 
 product 
used.
4. Boiler 
isolation 
valves:
 
Field supplied.  Full port ball valves are required.  Failure 
 
to use full port ball valves could result in a restricted flow 
 
rate through the boiler.
5. Check 
valves:
  Field supplied.  Check valves are required for 
 
installation as shown in FIG.’s 5-5 and 5-6.  Failure to 
 
install check valves could result in a reverse flow condition 
 
during pump(s) off cycle.
6.  Domestic indirect hot water isolation valves:
  Field supplied.  Full port ball valves are 
 
required.  Failure to use full port ball valves could 
 
result in a restricted flow rate through the boiler.
7.  Anti-scald mixing valve:
  Field supplied.  An anti-scald mixing valve is 
 
recommended when storing domestic hot water above 
 115°F 
(46°C).
8. Unions:
 
Field supplied.  Recommended for unit serviceability.
9. Pressure 
relief 
valve:
 
Factory supplied.  The pressure relief valve is sized to 
 ASME 
specifications.
10.  System temperature sensor:
  Lochinvar supplies a system temperature sensor. 
 
 
The sensor is to be installed in the heating loop 
 
downstream from the boiler hot water piping and 
  heating loop junction.  The sensor should be 
 
located far enough downstream to sense system diluted 
 water 
temperature. 
 NOTICE
Pump sizing and flow requirements are 
based on 20 feet (6 m) of black iron piping, 4 
- 90° elbows, and 2 - fully ported ball valves.
*When using copper with a 20° temperature 
rise increase piping to 3".
 NOTICE
5  
Hydronic piping 
(continued)
   
 NOTICE
A system supply sensor (factory supplied) 
MUST BE installed for proper boiler 
operation.
TEMPERATURE RISE APPLICATIONS
Model
MINIMUM PIPE
SIZE
20°F 25°F
30°F
35°F
GPM
FT/HD
GPM
FT/HD
GPM
FT/HD
GPM
FT/HD
1000
3"
55
31
40
20
38
18
32
13
1300
3"
65*
30
52
20
45
16
37
11
1500
3"
74*
33
60
23
51
18
42
12
0
10
20
30
40
50
60
0
10
20
30
40
50
60
70
80
90
SB1500
SB1300
SB1000
Pressure Drop vs Flow
Flow Rate (GPM) - Single Heat Exchanger Only
P
ressur
e Dr
op (F
eet of Head)
Single Hea
t Ex
changer Only
Figure 5-4  Pressure Drop vs. Flow 
Table 5A Sizing Information for Temperature Rise Applications_20°F, 25°F, 30°F and 35°F
11. Y-Strainer:
 
Field supplied.  A Y-strainer or equivalent multipurpose 
 
strainer is recommended at the inlet of the heat exchanger 
 
to remove system particles from older hydronic systems and 
 
protect newer systems.
31