Installation & Operation Manual
HOT WATER 
GENERATOR
    SYSTEM
CIRCULATOR
       AIR 
SEPARATOR
MAKE UP
 WATER
DRAIN POINT
  (TYPICAL)
SYSTEM SUPPLY
     SENSOR
BALL VALVE
 (TYPICAL)
HEAT EXCHANGER 1
BOILER PUMP
PRESSURE RELIEF
          VALVE
  FLOW CHECK
VALVE (TYPICAL)
PRESSURE REDUCING
            (VALVE)
EXPANSION
    TANK
UNION (TYPICAL)
TEMPERATURE/
PRESSURE GAUGE
TO FLOOR
 DRAIN (TYPICAL)
WATER GENERATOR
      CIRCULATOR
         (TYPICAL)
 BACK FLOW
PREVENTER
PRESSURE GAUGE
HEAT EXCHANGER 2
BOILER PUMP
Y-STRAINER
(RECOMMENDED)
TYPICAL)
MAY SUBSTITUTE LOW LOSS HEADER
TO
SY
ST
EM
FR
OM
SY
ST
EM
Figure 5-6 Multiple Boilers - Primary/Secondary Piping 
Model
Number of Units
2
3
4
5
6
7
8
Manifold Pipe Sizes in Inches (mm)
1000
4 (102)
5 (127)
6 (152)
6 (152)
8 (203)
8 (203)
8 (203)
1300
5 (127)
5 (127)
6 (152)
8 (203)
8 (203)
8 (203)
8 (203)
1500
5 (127)
6 (152)
6 (152)
8 (203)
8 (203)
8 (203)
10 (254)
5  
Hydronic piping 
(continued)
    
 NOTICE
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in 
operation to prevent short cycling and high limit issues.
 NOTICE
A system supply sensor (factory 
supplied) MUST BE installed for proper 
boiler operation.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible 
for all equipment and detailing required by local codes.