Lennox International Inc. GSB8-S 사용자 설명서

다운로드
페이지 36
14
ELECTRICAL WIRING
ELECTRIC POWER SUPPLY
Electrically bond boiler to ground in accordance with 
      
requirements of authority having jurisdiction.  Refer to:
USA- National Electrical Code, ANSI/NFPA 70.
• 
Canada - Canadian Electrical Code, Part I, CSA C22.1: 
• 
Safety Standard for Electrical Installations.
Run separate 115 volt circuit from separate overcurrent 
protective device in your electrical service entrance panel. 
This should be 15 ampere circuit. Locate shut-off switch 
at boiler. It must be turned off during any maintenance. 
Connect 115 volt electrical supply to primary leads on 24 
volt transformer. Solder and tape or securely fasten these 
connections with wire nuts.
Boiler, when installed, must be electrically grounded in 
accordance with requirements of the authority having 
jurisdiction or, in absence of such requirements, with 
National Electrical Code, ANSI/NFPA No. 70 and/or 
Canadian Electrical Code, Part I, CSA C22.1:  Safety 
Standard for Electrical Installations. Run 14 gauge or 
heavier copper wire from boiler to grounded connection in 
service panel or properly driven and electrically grounded 
ground rod.
!
WARNING
Turn off electrical power at fuse box before 
making any line voltage connections.  Follow 
local electrical codes.
INSTALL YOUR THERMOSTAT
Thermostat location has important effect on 
operation of your boiler system. BE SURE TO FOLLOW 
INSTRUCTIONS INCLUDED WITH YOUR THERMOSTAT.
Locate thermostat about fi ve feet above fl oor on inside 
wall. It may be mounted directly on wall or on vertically 
mounted outlet box. It should be sensing average room 
temperature, avoid following:
DEAD SPOTS: 
 Behind 
doors 
  Corners and alcoves
HOT SPOTS: 
  Concealed pipes  
Fireplace
 TV 
sets 
 Radios 
 Lamps
 Direct 
sunlight
 Kitchens 
COLD SPOTS: 
  Concealed pipes or ducts 
  Stairwells - drafts
  Doors – drafts
  Unheated rooms on other side of wall
Set heat anticipator at 0.4 amps for boilers equipped 
with standing pilot, and at 0.6 amps for boilers equipped 
with intermittent ignition. Connect 24 volt thermostat 
leads to two wires tagged “24 volt thermostat” on boiler. 
For boilers with 67D-1 fl oat type low water cut-off, two 
wires are black. One wire is located on secondary of 24 
volt transformer, second wire is located on pressure limit 
control. For boilers with PS-802 probe type low water 
cut-off, one wire is green and is located on terminal B of 
PS-802, second wire is black and located on pressure limit 
control.
ELECTRONIC THERMOSTATS
Certain types of electronic thermostats may lose their 
memory or shut down. With 67D-1 fl oat type low water 
cutoffs, this may occur each time thermostat calls for heat, 
due to internal circuit in vent damper. With PS-802 probe 
type low water cut off’s, this may occur each time low 
water cut off detects low water condition. If this is case, 
isolation relay is required for thermostat circuit. 24 volt 
single pole single throw (SPST) normally open (N.O.) relay 
is required, such as Honeywell R8222A or equivalent. Wire 
as shown in Fig. 10A or Fig. 10B.
VENT DAMPER
Boiler is equipped with factory wired harness with 4 pin 
molex plug, that plugs into 4 pin molex receptacle inside 
vent damper operator.
Vent damper must be connected for boiler to operate.
Wiring diagrams follow for various different models.
!
CAUTION
Label all wires prior to disconnection when 
servicing controls. Wiring errors can cause 
improper and dangerous operation. Verify 
proper operation after servicing.