Power
Installation
Unimode 9600   PN 51336:C    11/06/01
27
2.2  Power
WARNING: Several different sources of power can be connected to this panel.  
Disconnect all sources of power before servicing.  The panel and associated equipment 
may be damaged by removing and/or inserting cards, modules or interconnecting cables 
while this unit is energized.
2.2.1  AC Power and Earth Ground Connection 
Primary power required for the FACP is 120 VAC, 
60 Hz, 3.2 amps.  Overcurrent protection for this 
circuit must comply with Article 760 of the National 
Electrical Code (NEC) and/or local codes.  Use 14 
AWG (2.00 mm
2
) or larger wire with 600 volt 
insulation rating.  Make certain that the AC mains 
circuit breaker is off before making any wiring 
connections between the mains and the control panel.  Connect the wiring from the AC 
mains to TB1 on the FACP, being careful to observe proper connections. 
Connect a wire from the grounding stud in the cabinet to a known solid earth ground.  This 
connection is vital for maintaining the control panel’s immunity to unwanted transients 
generated by lightning and electrostatic discharge.  Apply AC power to the panel only 
after the system is completely installed and visually checked.  Note that AC power must be 
applied to the panel before installing the battery interconnect cable (refer to the following 
section).
2.2.2  Battery Power
Before connecting the batteries to the FACP, make 
certain that the interconnect cable between the batteries 
is not connected.  Do not connect the interconnect cable 
until the system is completely installed.  Observe 
polarity when connecting the batteries.  Connect the 
battery cable to TB2 on the main circuit board.  Refer  
"Power Supply Calculations" on page 127, for 
calculation of the correct battery rating.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and 
eyes and can destroy fabrics.  If contact is made with sulfuric acid, immediately flush the 
skin or eyes with water for 15 minutes and seek immediate medical attention.
2.2.3  DC Power Output Connection
All DC power outputs are power-limited. 
+BATTERY-
LCD DISPLAY
HOT
CB1
TB1
TB2
NEUT EARTH
-
-
+
+
Interconnect Cable
See Page
+   -   +   -   +   -
Figure 2.4 Power Outputs - 24 VDC
1   2   3   4   5   6
Power-limited Resettable Power
3.0 amperes max., 24 VDC nominal 
filtered, resettable power can be drawn 
from TB3 Terminals 1(+) and 2(-)
Power-limited Nonresettable Power #1
3.0 amperes max. , 24 VDC nominal 
filtered, nonresettable power can be 
drawn from TB3 Terminals 3(+) and 4(-)
Power-limited Nonresettable Power #2
3.0 amperes max. , 24 VDC nominal 
filtered, nonresettable power can be 
drawn from TB3 Terminals 5(+) and 6(-)
9600tb3.cdr