ADT Security Services 9600 사용자 설명서

다운로드
페이지 148
UL Power-limited Wiring Requirements
Installation
Unimode 9600   PN 51336:C    11/06/01
29
2.5  UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet.  
All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any 
nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit 
the cabinet through different knockouts and/or conduits.  A typical wiring diagram for the 
Unimode 9600 is shown below.
Figure 2.7 Typical UL Power-limited Wiring Requirements
Power-lim
ited Circu
its
Power-lim
ited Circu
its
Nonpowe
r-limited 
Circuits
Power-lim
ited
Circuits
4XTMF
SLC-2
ADT-UDACT
AC Powe
r
Nonpowe
r-limited 
To Batteri
es
Nonpowe
r-limited 
Circuits
Power-lim
ited
Circuits
To EIA-4
85 and 
24 VDC p
ower 
routed beh
ind 
board
m
s-9600wir
eroute.c
dr