prescribed  temperature-pressure  relief  valve  installed  in  the 
designated opening in the water heater in place of the factory 
furnished valve.
For safe operation of the water heater, the relief valve must not 
be removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly 
into the fitting of the water heater designed for the relief valve.  
Position  the  valve  downward  and  provide  tubing  so  that  any 
discharge will exit only within 6 inches (153 mm) above, or at any 
distance below the structural floor. Be certain that no contact is 
made with any live electrical part. The discharge opening must 
not  be  blocked  or  reduced  in  size  under  any  circumstances. 
Excessive length, over 30 feet (9.14 m), or use of more than 
four  elbows  can  cause  restriction  and  reduce  the  discharge 
capacity of the valve.
No  valve  or  other  obstruction  is  to  be  placed  between  the 
relief  valve  and  the  tank.  Do  not  connect  tubing  directly  to 
discharge drain unless a 6 inch air gap is provided. To prevent 
bodily  injury,  hazard  to  life,  or  property  damage,  the  relief 
valve must be allowed to discharge water in quantities should 
circumstances demand. If the discharge pipe is not connected 
to a drain or other suitable means, the water flow may cause 
property damage.
The Discharge Pipe:
•  Shall not be smaller in size than the outlet pipe size of the 
valve, or have any reducing couplings or other restrictions.
•  Shall not be plugged or blocked.
•  Shall be of material listed for hot water distribution.
•  Shall be installed so as to allow complete drainage of both the 
temperature-pressure relief valve, and the discharge pipe.
•  Shall terminate at an adequate drain.
•  Shall not have any shut-off valve between the relief valve and 
tank nor in the discharge pipe.
The  temperature-pressure  relief  valve  must  be  manually 
operated at least once a year.  Caution should be taken to 
ensure that (1) no one is in front of or around the outlet of the 
temperature-pressure relief valve discharge line, and (2) the 
water manually discharged will not cause any bodily injury or 
property damage because the water may be extremely hot.
If  after  manually  operating  the  valve,  it  fails  to  completely 
reset  and  continues  to  release  water,  immediately  close 
the cold water inlet to the water heater, follow the draining 
instructions,  and  replace  the  temperature-pressure  relief 
valve with a new one.
FIGURE 10.
Filling the Water Heater
Never use this water heater unless it is completely full of water. 
To prevent damage to the tank and heating element, the tank 
must be filled with water. Water must flow from the hot water 
faucet before turning “ON” power.
To fill the water heater with water:
•    Close the water heater drain valve by turning the handle to 
the right (clockwise). The drain valve is located on the lower 
front of the water heater.
•    Open the cold water supply valve to the water heater.
    NOTE: The cold water supply valve must be left open 
     when the water heater is in use.
•    To  insure  complete  filling  of  the  tank,  allow  air  to  exit  by 
opening the nearest hot water faucet. Allow water to run until 
a constant flow is obtained. This will let air out of the water 
heater and the piping.
•  Check all new water piping for leaks. Repair as needed.