Honeywell L4007 사용자 설명서

다운로드
페이지 20
L4006,7,8; L6006,7,8 AQUASTAT
®
 CONTROLLERS
60-2104—10
16
Adjust the control point to correspond with the boiler 
manufacturer recommendations. To adjust, insert a 
screwdriver in the slotted screw type head located beneath the 
window in the cover. Turn the scale to the desired control point.
Adjusting L6008G Interstage Differential
The L6008G Controller has an adjustable interstage 
differential. The set point adjustment knob determines the 
temperature at which the right switch operates. The left switch 
can be adjusted to operate from 3° F to 10° F (1.7° C to 5.6° C) 
above the point of operation of the right switch. See Figure 30 
for the operation of the L6008G. The interstage differential is 
adjusted by turning the star wheel with a narrow screwdriver 
inserted into the rectangular hole in the chassis. (See Fig. 32).
Fig. 32. Interstage differential adjustment on an L6008G.
L6008A Location Differential Calibration
The L6008A1093 is calibrated for applications where the bulb 
and controller case are located in the same control space.
If the bulb and controller case are located in separate rooms, 
and if the temperature in the two rooms is different, an 
adjustment is required. Adjust the dial setting (control space 
temperature setting) to compensate for the difference in 
temperature.
1. If the L6008A case is located in a room with a higher 
temperature than indicated on the dial setting, raise the 
dial setting the number of degrees listed in Table 3.
2. If the L6008A case is located in a room with a lower 
temperature than indicated on the dial setting, lower the 
dial setting the number of degrees listed in Table 3.
Table 3. Temperature Adjustments.
EXAMPLE:
In the example shown in Fig. 33, the L6008A case is 
located in a room with a lower temperature than the 
controlled space. Adjusting the controlled space setting (dial 
setting) is necessary to compensate for the temperature 
difference of 35° F (20° C) between the two rooms. Table 3 
indicates that the dial setting should be lowered 5° F (3° C) 
to compensate for the 35° F (20° C) temperature difference.
Manual Reset
If the device includes manual reset (L4006E, L4008E), be sure 
to press the (red) reset button on the front of the case to make 
sure that the controller is not locked out on safety. When 
checking the system, adjust the limit setting low enough so the 
temperature of the controlled medium reaches the high limit 
setting. When the limit setting is reached, the Aquastat 
Controller locks out and the burner shuts down. When the 
temperature of the controlled medium drops to the high limit 
setting, less the differential, push the manual reset button to 
make the system operative again. Reset the control to the 
proper high limit setting.
Fig. 33. L6008A calibration.
M8972
RIGHT
SWITCH
LEFT SWITCH
STAR WHEEL (INTERSTAGE
DIFFERENTIAL ADJUSTMENT)
1
1
SELECT MODELS HAVE FOUR TERMINALS.
Difference Between Desired 
Room Temperature and 
Case Temperature
Reduce Dial Setting
°F
°C
°F
°C
0
0
0
5
3
3/4
0.5
10
6
1-1/2
1
15
8
2
1
20
11
2-3/4
2
25
14
3-1/2
2
30
17
4-1/4
3
35
20
5
3
40
22
5-3/4
4
45
25
6-1/2
4
50
28
7
4
55
31
8
5
60
33
8-1/2
5
70
39
10
6
80
45
11-1/2
7
M8790A
WALL
L6008A
CASE
REMOTE
SENSING 
BULB
CONTROLLED
SPACE
TEMPERATURE
115
o
F (46
o
C)
ROOM 
TEMPERATURE
80
o
F (27
o
C)