Mitsubishi Electronics MR-J3 사용자 설명서
16 - 100
16. INDEXER POSITIONING OPERATION
16.12.4 When alarm or warning has occurred
POINT
Configure up a circuit which will detect the trouble (ALM) signal and turn off
the servo-on (RYn0) at occurrence of an alarm.
the servo-on (RYn0) at occurrence of an alarm.
(1) Alarms and warning list
When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or
warning has occurred, refer to (2), (3) in this section and take the appropriate action. When an alarm
occurs, ALM turns off.
After its cause has been removed, the alarm can be deactivated in any of the methods marked in the
alarm deactivation column.
warning has occurred, refer to (2), (3) in this section and take the appropriate action. When an alarm
occurs, ALM turns off.
After its cause has been removed, the alarm can be deactivated in any of the methods marked in the
alarm deactivation column.
Alarm deactivation
Display
Name
A90
Home positioning incomplete
warning
warning
A92
Open battery cable warning
A96 Home
position
setting
error
Display Name Power
OFF ON
(Note 3)
MR
Configurator
parameter
unit
(Note 2)
Alarm
reset
(RES)
A97 Next
station
warning
A10 Undervoltage
A99
Stroke limit warning
A12
Memory error 1 (RAM)
A9D CC-Link warning 1
A13 Clock
error
A9E CC-Link warning 2
Memory error 2
A9F
Battery warning
A15
(EEP-ROM)
AE0 Excessive
regeneration
warning
Encoder error 1
AE1
Overload
warning
1
A16
(At power on)
AE3 Absolute position counter warning
A17 Board
error
AE6 Servo forced stop warning
Memory error 3
Cooling fan speed reduction
A19
(Flash-ROM)
AE8
warning
A1A Motor
combination
error
AE9 Main circuit off warning
A20
Encoder error 2
AEC
Overload
warning
2
A24
Main circuit error
Warni
ngs
AED Output watt excess warning
A25 Absolute
position
erase
(Note 1)
(Note 1)
(Note 1)
A30 Regenerative
error
A31 Overspeed
A32 Overcurrent
A33 Overvoltage
A37 Parameter
error
A45
Main circuit device overheat
(Note 1)
(Note 1)
(Note 1)
A46 Servo
motor
overheat
(Note 1)
(Note 1)
(Note 1)
A47
Cooling fan alarm
A50 Overload
1
(Note 1)
(Note 1)
(Note 1)
A51 Overload
2
(Note 1)
(Note 1)
(Note 1)
A52 Error
excessive
A61 Operation
alarm
A8A
Serial communication time-out
error
error
A8D CC-Link
alarm
A8E Serial
communication
error
Ala
rm
s
888 Watchdog
Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.
2. Turns on RY(n 1)A or RY(n 3)A.
3. Clicking the "Alarm reset" button on the "Alarm display" screen of MR Configurator allows an alarm to be deactivated.
3. Clicking the "Alarm reset" button on the "Alarm display" screen of MR Configurator allows an alarm to be deactivated.
Pressing the "STOP RESET" key of the parameter unit allows an alarm to be deactivated.