16. INDEXER POSITIONING OPERATION 
 
16.12.4 When alarm or warning has occurred 
POINT 
 
Configure up a circuit which will detect the trouble (ALM) signal and turn off 
the servo-on (RYn0) at occurrence of an alarm. 
 
(1) Alarms and warning list 
When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or 
warning has occurred, refer to (2), (3) in this section and take the appropriate action. When an alarm 
occurs, ALM turns off. 
After its cause has been removed, the alarm can be deactivated in any of the methods marked   in the 
alarm deactivation column. 
 
Alarm deactivation 
  Display
Name 
A90 
Home positioning incomplete 
warning 
A92 
Open battery cable warning 
A96 Home 
position 
setting 
error 
  Display Name  Power 
OFF ON
(Note 3) 
MR 
Configurator
parameter 
unit 
(Note 2)
Alarm 
reset 
(RES) 
A97 Next 
station 
warning 
A10 Undervoltage 
 
 
 
A99 
Stroke limit warning 
A12 
Memory error 1 (RAM) 
 
 
 
A9D  CC-Link warning 1 
A13 Clock 
error 
 
 
 
A9E  CC-Link warning 2 
Memory error 2  
A9F 
Battery warning 
A15 
(EEP-ROM) 
 
 
 
AE0 Excessive 
regeneration 
warning 
Encoder error 1 
 AE1 
Overload 
warning 
A16 
(At power on) 
 
 
 
AE3  Absolute position counter warning
A17 Board 
error 
 
 
 
AE6  Servo forced stop warning 
Memory error 3  
Cooling fan speed reduction 
A19 
(Flash-ROM) 
 
 
 
AE8 
warning 
A1A Motor 
combination 
error 
 
 
 
AE9  Main circuit off warning 
A20 
Encoder error 2 
     AEC 
Overload 
warning 
A24 
Main circuit error 
 
 
 
Warni
ngs
 
AED  Output watt excess warning 
A25 Absolute 
position 
erase 
 
 
 
   
 
 
(Note 1) 
(Note 1) 
(Note 1)    
 
 
A30 Regenerative 
error 
 
 
 
   
 
 
A31 Overspeed 
 
 
 
   
 
 
A32 Overcurrent 
 
 
 
   
 
 
A33 Overvoltage 
 
 
 
   
 
 
A37 Parameter 
error 
 
 
 
   
 
 
A45 
Main circuit device overheat 
(Note 1) 
 
(Note 1) 
 
(Note 1)
 
   
 
 
A46 Servo 
motor 
overheat 
(Note 1) 
 
(Note 1) 
 
(Note 1)
 
   
 
 
A47 
Cooling fan alarm 
 
 
 
   
 
 
A50 Overload 
(Note 1) 
 
(Note 1) 
 
(Note 1)
 
   
 
 
A51 Overload 
(Note 1) 
 
(Note 1) 
 
(Note 1)
 
   
 
 
A52 Error 
excessive 
 
 
 
   
 
 
A61 Operation 
alarm 
 
 
 
   
 
 
A8A 
Serial communication time-out 
error 
 
 
 
   
 
 
A8D CC-Link 
alarm 
 
 
 
   
 
 
A8E Serial 
communication 
error 
 
 
 
   
 
 
Ala
rm
888 Watchdog 
 
 
 
   
 
 
Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence. 
2. Turns on RY(n 1)A or RY(n 3)A. 
3. Clicking the "Alarm reset" button on the "Alarm display" screen of MR Configurator allows an alarm to be deactivated. 
Pressing the "STOP RESET" key of the parameter unit allows an alarm to be deactivated.