TC12 Installation, Commissioning & Maintenance Handbook 
3.3.5  TCSU TC12 OTU Commissioning Procedure 
Reset OTU and select TCSU default configuration data. 
 
Enter the following commands: 
 
GME=249 (Access code) 
LRN=53    } 
CNN=117 } (Reset Codes) 
TKE=191  } 
 
Remove Mains power from the OTU, wait for a few seconds, then re-apply 
power. 
 
Note:  The value of 191 for TKE selects TCSU default configuration data but only 
when used to perform a complete OTU reset as detailed above. 
 
To set up OTU address and enable communication. 
 
Enter the following commands: 
 
GME=249    (Access Code) 
GAD=0 to 5 (OTU address - 6 OTUs on an Instation Modem) 
GOE=1        (Enables Control and Reply) 
 
Note 
The read-only handset command GDD can be used to indicate the default configuration 
data loaded when the OTU was last initialised. 
GDD = 0 Normal Default values 
GDD = 1 TCSU Default values 
 