met
e
rs
3–33
Any intelligent output terminal may be programmed to indicate a thermal warning [THM]. 
Parameter C061 determines the warning threshold. Please see 
 for more details.
“B” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
B012
Level of electronic 
thermal setting
Set a level between 50% and 
120% of the inverter rated 
current
✘ ✔
rated current for 
each inverter model
%
>b012 E-THM
LEVEL    0016.5A
B212
Level of electronic 
thermal setting, 2nd 
motor
Set a level between 50% and 
120% of the  inverter rated 
current
✘ ✔
rated current for 
each inverter model
%
>b212 2E-THM
LEVEL    0016.5A
B312
Level of electronic 
thermal setting, 3rd 
motor
Set a level between 50% and 
120% of the inverter rated 
current
✘ ✔
rated current for 
each inverter model
%
>b312     3E-THM
LEVEL    0016.5A
B013
Electronic thermal 
characteristic
Select from three curves, 
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting
✘ ✔
01
01
00
>b013 E-THM
CHAR        CRT
B213
Electronic thermal 
characteristic, 2nd 
motor
Select from three curves, 
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting
✘ ✔
01
01
00
>b213 2E-THM
CHAR        CRT
B313
Electronic thermal 
characteristic, 3rd motor
Select from three curves, 
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting
✘ ✔
01
01
00
>b313 3E-THM
CHAR        CRT
B015
Free setting, electronic 
thermal frequency (1) 
Range is 0.0 to 400.0 Hz
✘ ✔
0.
0.
0.
Hz
>b015 E-THM
F1        0000Hz
B016
Free setting, electronic 
thermal current (1)
Range is 0.0 to 1000. A
✘ ✔
0.0
0.0
0.0
A
>b016 E-THM
A1       0000.0A
B017
Free setting, electronic 
thermal frequency (2)
Range is 0.0 to 400.0 Hz
✘ ✔
0.
0.
0.
Hz
>b017 E-THM
F2        0000Hz
B018
Free setting, electronic 
thermal current (2)
Range is 0.0 to 1000. A
✘ ✔
0.0
0.0
0.0
A
>b018 E-THM
A2       0000.0A
B019
Free setting, electronic 
thermal frequency (3)
Range is 0.0 to 400.0 Hz
✘ ✔
0.
0.
0.
Hz
>b019 E-THM
F3        0000Hz
B020
Free setting, electronic 
thermal current (3)
Range is 0.0 to 1000. A
✘ ✔
0.0
0.0
0.0
A
>b020 E-THM
A3       0000.0A