Hitachi SJ300-037HFE 사용자 설명서
SJ300 Inverter
Configur
ing Dr
iv
e
P
a
ra
met
e
rs
3–33
Any intelligent output terminal may be programmed to indicate a thermal warning [THM].
Parameter C061 determines the warning threshold. Please see
Parameter C061 determines the warning threshold. Please see
for more details.
“B” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
B012
Level of electronic
thermal setting
thermal setting
Set a level between 50% and
120% of the inverter rated
current
120% of the inverter rated
current
✘ ✔
rated current for
each inverter model
%
>b012 E-THM
LEVEL 0016.5A
B212
Level of electronic
thermal setting, 2nd
motor
thermal setting, 2nd
motor
Set a level between 50% and
120% of the inverter rated
current
120% of the inverter rated
current
✘ ✔
rated current for
each inverter model
%
>b212 2E-THM
LEVEL 0016.5A
B312
Level of electronic
thermal setting, 3rd
motor
thermal setting, 3rd
motor
Set a level between 50% and
120% of the inverter rated
current
120% of the inverter rated
current
✘ ✔
rated current for
each inverter model
%
>b312 3E-THM
LEVEL 0016.5A
B013
Electronic thermal
characteristic
characteristic
Select from three curves,
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting
✘ ✔
01
01
00
—
>b013 E-THM
CHAR CRT
B213
Electronic thermal
characteristic, 2nd
motor
characteristic, 2nd
motor
Select from three curves,
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting
✘ ✔
01
01
00
—
>b213 2E-THM
CHAR CRT
B313
Electronic thermal
characteristic, 3rd motor
characteristic, 3rd motor
Select from three curves,
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting
✘ ✔
01
01
00
—
>b313 3E-THM
CHAR CRT
B015
Free setting, electronic
thermal frequency (1)
thermal frequency (1)
Range is 0.0 to 400.0 Hz
✘ ✔
0.
0.
0.
Hz
>b015 E-THM
F1 0000Hz
B016
Free setting, electronic
thermal current (1)
thermal current (1)
Range is 0.0 to 1000. A
✘ ✔
0.0
0.0
0.0
A
>b016 E-THM
A1 0000.0A
B017
Free setting, electronic
thermal frequency (2)
thermal frequency (2)
Range is 0.0 to 400.0 Hz
✘ ✔
0.
0.
0.
Hz
>b017 E-THM
F2 0000Hz
B018
Free setting, electronic
thermal current (2)
thermal current (2)
Range is 0.0 to 1000. A
✘ ✔
0.0
0.0
0.0
A
>b018 E-THM
A2 0000.0A
B019
Free setting, electronic
thermal frequency (3)
thermal frequency (3)
Range is 0.0 to 400.0 Hz
✘ ✔
0.
0.
0.
Hz
>b019 E-THM
F3 0000Hz
B020
Free setting, electronic
thermal current (3)
thermal current (3)
Range is 0.0 to 1000. A
✘ ✔
0.0
0.0
0.0
A
>b020 E-THM
A3 0000.0A