“B” Group: Fine-Tuning Functions
Configur
ing Dr
iv
P
a
ra
meters
3–34
Overload
Restriction
If the inverter’s output current exceeds a 
preset current level you specify during 
acceleration or constant speed, the 
overload restriction feature automati-
cally reduces the output frequency to 
restrict the overload. This feature does 
not generate an alarm or trip event. You 
can instruct the inverter to apply 
overload restriction only during 
constant speed, thus allowing higher 
currents for acceleration. Or, you may 
use the same threshold for both acceler-
ation and constant speed. In the case of 
controlled deceleration, the inverter monitors both output current and DC bus voltage. The 
inverter will increase output frequency to try to avoid a trip due to over-current or over-voltage 
(due to regeneration).
When the inverter detects an overload, it must decelerate the motor to reduce the current until it 
is less than the threshold. You can choose the rate of deceleration that the inverter uses to lower 
the output current. 
Motor 
Current
Output
Frequency
B023
B022
t
restriction area
0
t
“B” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
B021
Overload restriction 
operation mode
Select the operating mode 
during overload conditions, 
four options, option codes:
00 Disabled
01 Enabled for acceleration 
and constant speed
02 Enabled for constant 
speed only
03 Enabled for accel, decel, 
and constant speed
✘ ✔
01
01
01
>b021 OLOAD
1MODE        ON
B022
Overload restriction 
setting
Sets the level for overload 
restriction, between 50% 
and 200% of the rated 
current of the inverter, 
setting resolution is 1% of 
rated current
✘ ✔
rated current times 
1.50
A
>b022 OLOAD
1LEVEL   0024.8A
B023
Deceleration rate at 
overload restriction
Sets the deceleration rate 
when inverter detects 
overload, range is 0.1 to 
30.0, resolution is 0.1.
✘ ✔ 1.00 1.00 1.00
sec.
>b023 OLOAD
1CONST     01.00
B024
Overload restriction 
operation mode (2)
Select the operating mode 
during motor overload 
conditions, four options,  
option codes:
00 Disabled
01 Enabled for acceleration 
and constant speed
02 Enabled for constant 
speed only
03 Enabled for accel, decel, 
and constant speed
✘ ✔
01
01
01
>b024 OLOAD
2MODE        ON