“B” Group: Fine-Tuning Functions
Configur
ing Dr
iv
P
a
ra
meters
3–36
Software Lock 
Mode
The software lock function keeps personnel from accidentally changing parameters in the 
inverter memory. Use B031 to select from various protection levels.
The table below lists all combinations of B031 option codes and the 
ON/OFF state of the [SFT] input. Each Check 
✔ or Ex ✘ indicates 
whether the corresponding parameter(s) can be edited. The Standard 
Parameters column below lists Low and High level access for some 
lock modes. These refer to the parameter tables throughout this 
chapter, each of which includes a column titled Run Mode Edit as 
shown to the right. The two marks (Check 
✔ or Ex ✘) under the “Lo 
Hi” subtitle indicate whether Low-level and/or High-level access 
applies to each parameter as defined in the table below. In some lock modes, you can edit only 
F001 and the Multi-speed parameter group that includes A020, A220, A320, A021–A035, and 
A038 (Jog). However, it does not include A019, Multi-speed operation selection. The editing 
access to B031 itself is unique, and is specified in the right-most two columns below.
NOTE: Since the software lock function B031 is always accessible when the motor is stopped, 
this feature is not the same as password protection used in other industrial control devices.
NOTE: To disable parameter editing when using B031 lock modes 00 and 01, assign the [SFT] 
function to one of the intelligent input terminals. See 
.
B031 
Lock 
Mode
[SFT] 
Intelligent 
Input
Standard Parameters
F001 and 
Multi-speed
B031
Stop
Run
Stop or Run
Stop
Run
00
OFF
Low-level
ON
01
OFF
Low-level
ON
02
(ignored)
03
(ignored)
10
(ignored)
High-level
Run 
Mode 
Edit
Lo Hi
✘ ✔
“B” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–F
(Jpn)
B031
Software lock mode 
selection
Prevents parameter changes 
in five options:
00 Low-level access, [SFT] 
input blocks all edits
01 Low-level access, [SFT] 
input blocks edits 
(except F001 and Multi-
speed parameters)
02 No access to edits
03 No access to edits except 
F001 and Multi-speed 
parameters
10 High-level access, 
including B031
✘ ✔
01
01
01
>b031 S-LOCK
Mode        MD1