Configur
ing Dr
iv
e
P
a
ra
meters
3–66
NOTE: Parameters P044 to P049 are available only in inverters with manufacturing code
x8K xxxxxx xxxxx or later. The manufacturing code is printed on the product specifications
labels, located on the front and side of the inverter housing.
x8K xxxxxx xxxxx or later. The manufacturing code is printed on the product specifications
labels, located on the front and side of the inverter housing.
P022
Feed-forward gain
setting
setting
Range is 0.00 top 99.99 /
100.0
100.0
✘ ✔ 0.00 0.00 0.00
—
>P022 FEEDBACK
FFWG 000.00
P023
Position loop gain
setting
setting
Range is 0.00 to 99.99 /
100.0
100.0
✘ ✔ 0.50 0.50 0.50
—
>P023 FEEDBACK
G 000.50
P025
Temperature compensa-
tion thermistor enable
tion thermistor enable
Allows for motor-mounted
thermistor to calibrate
output to motor temperature
Two option codes:
00 Disable
01 Enable
thermistor to calibrate
output to motor temperature
Two option codes:
00 Disable
01 Enable
✘ ✔
00
00
00
—
>P025 FEEDBACK
R2-ADJ OFF
P026
Over-speed error
detection level setting
detection level setting
Range is 0.0 to 150.0%
✘ ✔
135.0
135.0
135.0
%
>P026 FEEDBACK
0SPD 135.0%
P027
Speed deviation error
detection level setting
detection level setting
Range is 0.00 to 99.99 /
120Hz
120Hz
✘ ✔ 7.50 7.50 7.50
—
>P027 FEEDBACK
NER 007.50Hz
P031
Accel/decel time input
selection
selection
Three options:
00 Inverter
01 Expansion card 1
02 Expansion card 2
00 Inverter
01 Expansion card 1
02 Expansion card 2
✘ ✘
00
00
00
—
>P031 ACC/DEC
SELECT REM
P032
Positioning command
input selection
input selection
Three options:
00 Inverter
01 Expansion card 1
02 Expansion card 2
00 Inverter
01 Expansion card 1
02 Expansion card 2
✘ ✔
00
00
00
—
>P032 P-SET
SELECT REM
P044
DeviceNet comm
watchdog timer
watchdog timer
Range is 0.00 99.99 seconds
✘ ✘
1.00
1.00
1.00
—
>P044 DEVICENET
TIMER 01.00s
P045
Inverter action on
DeviceNet comm error
DeviceNet comm error
Five options:
00 Trip
01 Decelerate and trip
02 Hold last speed
03 Free run stop
04 Decelerate and stop
00 Trip
01 Decelerate and trip
02 Hold last speed
03 Free run stop
04 Decelerate and stop
✘ ✘
01
01
01
—
>P045 DEVICENET
T-OUT FTP
P046
DeviceNet polled I/O:
Output instance number
Output instance number
Three settings:
20, 21, 100
20, 21, 100
✘ ✘
21
21
21
—
>P046 DEVICENET
O-AS-INS 021
P047
DeviceNet polled I/O:
Input instance number
Input instance number
Three settings:
70, 71, 101
70, 71, 101
✘ ✘
71
71
71
—
>P047 DEVICENET
O-AS-INS 071
P048
Inverter action on
DeviceNet idle mode
DeviceNet idle mode
Five options:
00 Trip
01 Decelerate and trip
02 Hold last speed
03 Free run stop
04 Decelerate and stop
00 Trip
01 Decelerate and trip
02 Hold last speed
03 Free run stop
04 Decelerate and stop
✘ ✘
01
01
01
—
>P048 DEVICENET
IDLE FTP
P049
DeviceNet motor poles
setting for RPM
setting for RPM
Range is 00 to 38 (even
numbers only)
numbers only)
✘ ✘
0
0
0
poles
>P049 DEVICENET
P 00P
“P” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)