Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
Programming Error Codes
Configur
ing Dr
iv
P
a
ra
meters
3–68
Programming Error Codes
The SJ300 inverter operator keypad displays a special code (begins with the   character) to 
indicate a programming error. Programming errors exist when one parameter conflicts with the 
meaningful range permitted by related parameter(s). Note that particular real-time frequency 
(speed) input levels can cause a conflict in some situations. After a conflict exists, the error 
code will appear on the display, or you can view it later with D090 in Monitor Mode. Also, the 
PGM LED on the display will flash ON/OFF when programming. These indications are 
automatically cleared when the parameter is corrected to the allowed range.  
Programming Error 
Code
Parameter out of bounds
Boundary defined by...
Code
Description
<, >
Code
Description
001 201
A061 / A261
Frequency upper limit 
setting; 1st, 2nd motor
>
A004 / 
A204 / 
A304
Maximum frequency;
1st, 2nd, 3rd motor
002 202
A062 / A262
Frequency lower limit 
setting; 1st, 2nd motor
>
004 204 304
A003 / A203 / 
A303
Base frequency setting; 
1st, 2nd, 3rd motor
>
005 205 305
F001,
A020 / A220 / 
A320
Output frequency setting, 
Multi-speed freq. setting; 
1st, 2nd, 3rd motor
>
006 206 306
A021 to A035 Multi-speed freq. settings
>
012 212
A062 / A262
Frequency lower limit 
setting; 1st, 2nd motor
>
A061 / A261
Frequency upper limit setting; 
1st, 2nd motor
015 215
F001,
A020 / A220
Output frequency setting, 
Multi-speed freq. setting; 
1st, 2nd motor
>
016 216
A021 to A035 Multi-speed freq. settings
>
021 221
A061 / A261
Frequency upper limit 
setting; 1st, 2nd motor
<
A062 / A262
Frequency lower limit setting; 
1st, 2nd motor
025 225
F001,
A020 / A220
Output frequency setting, 
Multi-speed freq. setting; 
1st, 2nd motor
<
031 231
A061 / A261
Frequency upper limit 
setting; 1st, 2nd motor
<
B082
Start frequency adjustment
032 232
A062 / A262
Frequency lower limit 
setting; 1st, 2nd motor
<
035 235 335
F001,
A020 / A220 / 
A320
Output frequency setting, 
Multi-speed freq. setting; 
1st, 2nd, 3rd motor
<
036
A021 to A035 Multi-speed freq. settings
<
037
A038
Jog frequency setting
<
085 285 385
F001,
A020 / A220 / 
A320
Output frequency setting, 
Multi-speed freq. setting; 
1st, 2nd, 3rd motor
>f-x,
<f+x
A063 ± A064
A065 ± A066
A067 ± A068
Jump (center) frequency ± 
jump (hysteresis) frequency 
width setting
(See note after table)
086
A021 to A035 Multi-speed freq. settings
>f-x,
<f+x