Using Intelligent Input Terminals
Oper
ations
a
nd Moni
tor
ing
4–12
Wiring Diagram 
Conventions
The input wiring diagrams in this chapter are examples only. Default and non-default input 
terminal assignments are noted throughout; your particular assignments may be different. The 
wiring diagrams show the –xFU/–xFR model default [P24]–[PLC] jumper position (U.S./Jpn 
versions), as shown below on the left. The common (return) for inputs is [CM1] in this case. 
The diagram on the right shows the default jumper position and example input wiring for –xFE 
models (Europe version). For this case, the common (return) for inputs is [P24]. Be sure the 
jumper position and return terminal used match your application wiring needs.
Forward Run/
Stop and Reverse 
Run/Stop 
Commands
When you input the Run command via the dedicated terminal [FW], the inverter executes the 
Forward Run command (high) or Stop command (low). When you input the Run command via 
the programmable terminal [RV], the inverter executes the Reverse Run command (high) or 
Stop command (low).
NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single Run 
key issues a Run FWD command or Run REV command. However, it has no effect on the [FW] 
and [RV] input terminal operation.
WARNING: If the power is turned ON and the Run command is already active, the motor 
starts rotation and is dangerous! Before turning power ON, confirm that the external Run 
command is not active.
5
3
1
4
2
FW
TH
PLC
P24
CM1
5
3
1
4
2
FW
TH
PLC
P24
CM1
Default jumper
position [P24]–[PLC] 
and wiring example 
(used throughout this 
chapter)
–xFU/–xFR models (U.S./Jpn versions):
–xFE models (Europe version):
Default jumper
position [PLC]–[CM1] 
and wiring example
return
return
RV
FW
RV
FW
Opt.
Code
Symbol
Function Name
State
Description
FW
Forward Run/Stop
ON
Inverter is in Run Mode, motor runs 
forward
OFF
Inverter is in Stop Mode, motor stops
01
RV
Reverse Run/Stop
ON
Inverter is in Run Mode, motor runs 
reverse
OFF
Inverter is in Stop Mode, motor stops
Valid for 
inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
A002 = 01
Notes: 
• 
When the Forward Run and Reverse Run 
commands are active at the same time, the 
inverter enters the Stop Mode.
• When a terminal associated with either [FW] 
or [RV] function is configured for normally 
closed
, the motor starts rotation when that 
terminal is disconnected or otherwise has no 
input voltage.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
Example: (Default input configuration 
shown—see page 
. Jumper position 
shown is for –xFU/-xFR models; for –xFE 
models, see examples above.)
RV
FW