Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–13
Multi-Speed 
Select
The inverter can store up to 16 different fixed target frequencies (speeds) in parameters A020 
to A035. Binary inputs select the speed through four of the intelligent terminals configured as 
binary-encoded inputs CF1 to CF4 per the table. These can be any of the eight inputs, and in 
any order. You can use fewer inputs if you need eight or fewer speeds.
NOTE: When choosing a subset of speeds to use, always start at the top of the table, and with 
the least-significant bit: CF1, CF2, etc.
The example with eight speeds in the figure below shows how input switches configured for 
CF1 – CF3 functions can change the motor speed in real time. 
Multi-speed Override Feature - The multi-speed function can selectively override the 
external analog speed reference input. When the Frequency Source Setting parameter 
A001=01, the control terminal inputs determine the output frequency. At the same time, the 
inverter can use multi-speed select for output frequency if one or more intelligent inputs are 
configured as a CF type (CF1 to CF4). When all CF input(s) are OFF, the control terminal input 
determines the output frequency normally. When one or more CF input(s) are ON, then the 
corresponding multi-speed setting (see the table above) overrides and becomes the output 
frequency.  
Multi-
speed
Input Function
Multi-
speed
Input Function
CF4
CF3
CF2
CF1
CF4
CF3
CF2
CF1
Speed  0
0
0
0
0
Speed  8
1
0
0
0
Speed  1
0
0
0
1
Speed  9
1
0
0
1
Speed 2
0
0
1
0
Speed 10
1
0
1
0
Speed 3
0
0
1
1
Speed 11
1
0
1
1
Speed 4
0
1
0
0
Speed 12
1
1
0
0
Speed 5
0
1
0
1
Speed 13
1
1
0
1
Speed 6
0
1
1
0
Speed 14
1
1
1
0
Speed 7
0
1
1
1
Speed 15
1
1
1
1
0th
CF1
CF2
CF3
1st
2nd
6th
5th
4th
3rd
7th
Speed
Switches
Fwd Run
t