Using Intelligent Input Terminals
Oper
ations
a
nd Moni
tor
ing
4–20
Free-run Stop
When the terminal [FRS] is turned ON, the inverter turns OFF the output and the motor enters 
the free-run state (coasting). If terminal [FRS] is turned OFF, the output resumes sending power 
to the motor if the Run command is still active. The free-run stop feature works with other 
parameters to provide flexibility in stopping and starting motor rotation.
In the figure below, parameter B088 selects whether the inverter resumes operation from 0 Hz 
(left graph) or the current motor rotation speed (right graph) when the [FRS] terminal turns 
OFF. The application determines the best setting.
Parameter B003 specifies a delay time before resuming operation from a free-run stop. To 
disable this feature, use a zero delay time.
FRS
Switches
Motor 
speed
[FW, RV]
Zero-frequency start
FRS
Switches
Motor 
speed
Resume from current speed
wait time
[FW, RV]
B003
B088=01
B088=00
Resume from 0Hz
t
t
Opt.
Code
Symbol
Function Name
Input 
State
Description
11
FRS
Free-run Stop
ON
Causes output to turn OFF, allowing 
motor to free run (coast) to stop
OFF
Output operates normally, so controlled 
deceleration stops motor
Valid for 
inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
B003, B088, C011 to C018
Notes: 
• 
When you want the [FRS] terminal to be 
active low (normally closed logic), change 
the setting (C011 to C018) that corresponds 
to the input (C001 to C008) that is assigned 
the [FRS] function.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
Example: (Default input configuration 
shown—see page 
. Jumper position 
shown is for –xFU/-xFR models; for –xFE 
models, see page 
.)
FRS