Using Intelligent Input Terminals
Oper
ations
a
nd Moni
tor
ing
4–18
Set Second or 
Third Motors
If you assign the [SET] or [SET3] functions to an intelligent input terminal, you can select 
between two or three sets of motor parameters. You may assign one or both of these functions. 
These second and third parameters store alternate sets of motor characteristics. When terminal 
[SET] or [SET3] is turned ON, the inverter will use the second or third set of parameters 
accordingly, generating the frequency output to the motor. When changing the state of the 
[SET] or [SET3] input terminal, the change will not take effect until the inverter is stopped.
When you turn ON the [SET] or [SET3] input, the inverter operates per the second or third set 
of parameters, respectively. When the terminal is turned OFF, the output function returns to the 
original settings (first set of motor parameters). Refer to 
 for details.
Opt.
Code
Symbol
Function Name
Input 
State
Description
08
SET
Set 2nd Motor
ON
causes the inverter to use the 2nd set of 
motor parameters for generating the 
frequency output to motor
OFF
causes the inverter to default to the 1st 
(main) set of motor parameters for gener-
ating the frequency output to motor
17
SET3
Set 3rd Motor
ON
causes the inverter to use the 3rd set of 
motor parameters for generating the 
frequency output to motor
OFF
causes the inverter to default to the 1st 
(main) set of motor parameters for gener-
ating the frequency output to motor
Valid for 
inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
(none)
Notes: 
• 
If the terminal state is changed while the 
inverter is running, the inverter continues 
using the current set of parameters until the 
inverter is stopped.
• If both SET and SET3 are ON at the same 
time, SET prevails and the 2nd motor param-
eters are in effect.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on pag
.
Example: (Requires input configuration—
see page 
. Jumper position shown is 
for –xFU/-xFR models; for –xFE models, 
see page 
.)
SET
SET3