Hitachi SJ300-037HFE 사용자 설명서
SJ300 Inverter
Oper
ati
ons
ons
and Monitor
ing
4–41
Expansion Card
Input Signals
Input Signals
Other inputs listed below require the expansion card SJ-FB Encoder Feedback. Please see the
SJ-FB manual for more information.
SJ-FB manual for more information.
The diagram below shows how the Input/Output connections for the SJ–FB feedback board.
The inverter’s internal connections and parameter configuration make these signals available on
intelligent input and output terminals.
The inverter’s internal connections and parameter configuration make these signals available on
intelligent input and output terminals.
The information on outputs related to the SJ-FB expansion card is in
.
Opt.
Code
Symbol
Function Name
Description
45
ORT
Orientation
Orientation (home search sequence)
46
LAC
LAD Cancel
Cancels the linear acceleration/decelera-
tion position control in the feedback card
tion position control in the feedback card
47
PCLR
Position deviation clear
Forces the position error to zero
48
STAT
Pulse train input enable
Starts the pulse train control of motor
frequency
frequency
SJ300 inverter
SJ-FB Feedback
Expansion Card
Input assignments
Output assignments
Input
terminals
Output
terminals
Control and logic connector
ORT
LAC
PCLR
STAT
ZS
DSE
POK