SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–43
Run Signal
When the [RUN] signal is selected as an 
intelligent output terminal, the inverter 
outputs a signal on that terminal when it is 
in Run Mode. The output logic is active 
low, and is the open collector type (switch 
to common).
 
NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to 
prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s 
output transistor.
Opt.
Code
Symbol
Function Name
Output 
State
Description
00
RUN
Run signal
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Valid for 
outputs:
11, 12, 13, 14, 15,
AL0 – AL2
Required 
settings:
(none)
Notes: 
• 
The inverter outputs the [RUN] signal 
whenever the inverter output exceeds the start 
frequency specified by parameter B082. The 
start frequency is the initial inverter output 
frequency when it turns ON.
[FW, RV]
Motor 
speed
Run 
Signal
start freq.
B82
ON
t
RY
+
See I/O specs on pag
Inverter output terminal circuit
CM2
13
14
15
11
12
Example: (Default output configuration 
shown—see pag
.)
RUN