Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–47
Output Deviation 
for PID Control
The PID loop error is defined as the 
magnitude (absolute value) of the differ-
ence between the Setpoint (target value) 
and the Process Variable (actual value). 
When the error magnitude exceeds the 
preset value for C044, the [OD] terminal 
signal turns ON. Refer to 
NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to 
prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s 
output transistor.
Opt.
Code
Symbol Function Name
Output 
State
Description
04
OD
Output deviation 
for PID control
ON
when PID error is more than the set 
threshold for the deviation signal
OFF
when PID error is less than the set thresh-
old for the deviation signal
Valid for 
outputs:
11, 12, 13, 14, 15,
AL0 – AL2
Required 
settings:
C044
Notes: 
• 
The default deviation value is set to 3%. To 
change this value, change parameter C044 
(deviation level).
Set 
value
[OD] 
Signal
Error 
(SP-PV)
C044
C044
ON
ON
t
Process variable
Setpoint
RY
+
See I/O specs on page 
.
Inverter output terminal circuit
CM2
13
14
15
11
12
Example: (Requires output configuration—
see page 
):
OD