Using Intelligent Output Terminals
Oper
ations
a
nd Moni
tor
ing
4–50
Over-torque 
Signal
The Over-torque function [OTQ] turns ON when the estimated value of output torque of motor 
increases more than the arbitrary level set for the output. Recall that the torque limit function, 
covered in 
, actually limits the torque during certain operating 
conditions. Instead, the over-torque output feature only monitors the torque, turning ON output 
[OTQ] if the torque is above programmable thresholds you set. The [OTQ] function is valid 
only for sensorless vector control, 0-Hz domain sensorless vector control, or vector control 
with sensor. Do not use the [OTQ] output, except for these inverter operational modes.
The assignment of the Over-torque function to an output terminal [OTQ] is detailed in the 
following table.
Code
Function/Description
Data or Range
C055
Over-torque, forward-driving level setting
0 to 200%
C056
Over-torque, reverse-regenerating, level setting
0 to 200%
C057
Over-torque, reverse-driving, level setting
0 to 200%
C058
Over-torque, forward-regenerating, level setting
0 to 200%
C021
to
C025
Intelligent output terminal [11] to [15] function
07
Opt.
Code
Symbol
Function Name
Output 
State
Description
07
OTQ
Over-torque
ON
when estimated torque exceeds the level 
set in C055 to C058
OFF
when estimated torque is below the levels 
set in C055 to C058
Valid for 
outputs:
11, 12, 13, 14, 15,
AL0 – AL2
Required 
settings:
C055, C056, C057, C058
A044 = 03 or 04 or 05
Notes: 
• 
This output is valid only for  sensorless 
vector control, 0-Hz domain sensorless vector 
control, or vector control with sensor
CM2
13
14
15
11
12
See I/O specs on page 
.
Inverter output 
terminal circuit
RY
+
Example: (Default output configuration 
shown—see pag
OTQ