Using Intelligent Output Terminals
Oper
ations
a
nd Moni
tor
ing
4–52
In the following examples, t
0
= instantaneous power failure time, t
1
 = allowable under-voltage / 
power failure time (B002), and t
2
= retry wait time (B003).
Opt.
Code
Symbol
Function Name
Output 
State
Description
08
IP
Instantaneous 
Power Failure
ON
when the inverter detects a loss of input 
power
OFF
when the inverter has input power
09
UV
Under-voltage 
condition
ON
when the inverter input power is less than 
the specified input range
OFF
when the inverter input power is within 
the voltage specification
Valid for 
outputs:
11, 12, 13, 14, 15,
AL0 – AL2
Required 
settings:
B001, B002, B003, B004, 
B005, B007
Notes: 
• 
If an over-voltage or over-current trip occurs 
during the deceleration and an instantaneous 
power failure error (E16) is displayed the 
inverter goes into free-run stop. In this case 
make the deceleration time longer.
• When connecting control power supply 
terminals [Ro]-[To] to the DC bus [P]-[N], an 
under-voltage may be detected at power-off 
and cause a trip. If this is undesirable, set 
B004 to 00 or 02.
• Frequency matching: The inverter reads the 
motor RPM and direction. If this speed is 
higher than the matching setting (B007), the 
inverter waits until they are equal and then 
engages the output to drive the motor 
(example 3). If the actual motor speed is less 
than the restart frequency setting, the inverter 
waits for t
2
 (value in B003) and restarts from 
0 Hz (example 4). The display shows 
oooo
” during an actual frequency 
matching event.
See I/O specs on page 
.
Inverter output 
terminal circuit
CM2
13
14
15
11
12
Example: (Default output configuration 
shown—see page 
RY
+
IP
Power supply
Inverter output
Motor
frequency
After waiting for t
2
 seconds when t
< t
1
; restart
Example 1: Power failure within allowed limits; resume
Example 2: Power failure longer than limits; trip
t
0
t
1
t
2
Power supply
Inverter output
Motor
frequency
t
0
t
1
Inverter trips when t
0
 > t
1
Free-run
Free-run
t