Using Intelligent Output Terminals
Oper
ations
a
nd Moni
tor
ing
4–54
Torque Limit 
Signal
The Torque Limit output [TRQ] works in conjunction with the torque limit function covered in 
the intelligent input section. The torque limit function limits the motor torque according to the 
criteria selected by parameter B040. When torque limiting occurs, the [TRQ] output turns ON, 
then going OFF automatically when the output torque falls below the specified limits. See 
 in the intelligent input section.
Run Time / 
Power-On Time 
Over Signals
SJ300 Series inverters accumulate the total hours in Run Mode (run time) and the total hours of 
power-ON time. You can set thresholds for these accumulating timers. Once the threshold is 
exceeded, an output terminal will turn ON. One use of this is for preventative maintenance. A 
signal light or audible alert could signal the need for servicing, calibration, etc.
Opt.
Code
Symbol
Function Name
Output 
State
Description
10
TRQ
Torque Limit
ON
when the inverter is limiting torque
OFF
when the inverter is not limiting torque
Valid for 
outputs:
11, 12, 13, 14, 15,
AL0 – AL2
Required 
settings:
B040... if B040=00 then 
B041, B042, B043, B044 are 
required
Notes: 
• 
The Torque Limit input [TL] must be ON in 
order to enable torque limiting and its related 
output, [TRQ].
CM2
13
14
15
11
12
See I/O specs on page 
.
Inverter output 
terminal circuit
RY
+
Example: (Requires output configuration—
see page 
.)
TRQ
Opt.
Code
Symbol
Function Name
Output 
State
Description
11
RNT
Run Time Over
ON
when the accumulated time spent in Run 
Mode exceeds the limit (B034)
OFF
when the accumulated time in Run Mode 
is still less than the limit (B034)
12
ONT
Power-ON Time 
Over 
ON
when the accumulated power-ON time 
exceeds the limit (B034)
OFF
when the accumulated power-ON time is 
less than the limit (B034)