The left graph below shows the region for possible free-setting curves. The right graph below 
shows an example curve defined by three data points specified by B015 – B020.
Suppose the electronic thermal setting (B012) is set to 44 Amperes. The graph below shows the 
effect of the free setting torque characteristic curve. For example, at (B017) Hz, the output 
current level to cause overheating in a fixed time period is reduced to (B018) A. Points (x), (y), 
and (z) show the adjusted trip current levels in those conditions for given trip times.
Thermal Warning Output – Using parameter C061, you can set the threshold from 0 to 100% 
of trip level for turning ON the intelligent output [THM] at that level. In this way, the inverter 
provides an early warning before the electronic thermal overload trips and turns OFF the output 
to the motor.
Opt.
Code
Symbol Function Name
Output 
State
Description
13
THM
Thermal Warning
ON
when the electronic thermal calculation 
exceeds the set limit
OFF
when the electronic thermal calculation is 
less than the set limit
Valid for 
outputs:
11, 12, 13, 14, 15,
AL0 – AL2
Required 
settings:
C061
Notes: 
• 
The electronic thermal overload function uses 
the output current and time to calculate 
thermal heating of the motor.
• The thermistor input of the inverter is a 
separate function from the electronic thermal 
function. You can set a threshold for it to 
cause a trip alarm at a particular thermistor 
resistance.
Output
current (A)
Setting range
max. freq.
B020
B018
B016
B015 B017 B019 Ax04
Trip current 
reduction 
factor
Output freq.
x 1.0
x 0.8
0
5
400
Hz
Hz
0
Trip
time (s)
(x) = B018 value x 116%
(y) = B018 value x 120%
(z) = B018 value x 150%
Reduced trip current at (B017) Hz
60
0
0.5
(x)
(y)
(z)
A
CM2
13
14
15
11
12
See I/O specs 
on pag
.
Inverter output 
terminal circuit
Example: (Requires output configuration—
see page 
.)
RY
+
THM