Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–67
Auto-tuning of 
Motor Constants
The SJ300 inverter features auto-tuning, which detects and records the motor characteristic 
parameters to use in all vector control modes. Auto-tuning determines the resistance and induc-
tance of motor windings. Therefore, the motor must be connected to the inverter for this proce-
dure. Note that the auto-tuning feature is not associated with PID loop operation, which is 
common on some control devices. The auto-tuning procedure must be conducted while the 
inverter is stopped (not in Run mode), so it can use special output pulses to detect motor 
characteristics.
When using the inverter in sensorless vector control, sensorless vector control - 0Hz domain, or 
vector control with encoder feedback, the motor circuit constants are important. If they are 
unknown, then you must first conduct the auto-tuning procedure. The inverter will determine 
the constants and write new values for the related “H” Group settings. The auto-tuning proce-
dure requires that the inverter be configured to operate the 1st motor (do not set the inverter to 
use 2nd and 3rd motor data during an auto-tuning procedure).
Please read the following Warning before running the auto-tuning procedure on the next page.
WARNING: You may need to disconnect the load from the motor before performing auto-
tuning. The inverter runs the motor forward and backward for several seconds without regard to 
load movement limits.
Func.
Name
Range
Notes
H001
Auto-tuning setting
00
Disabled
01
Enabled, without motor rotation
02
Enabled, with motor rotation
H002
Motor data selection, 1st motor
00
Standard motor parameters
01
Auto-tuning parameters
02
Adaptive tuning parameters
H003
Motor capacity, 1st motor
0.2 – 75,
0.2 – 160
kW, up to –550xxx models
kW, –750xxx to –1500xxx 
models
H004
Motor poles setting, 1st motor
2 / 4 / 6 / 8
Units: poles
H030
Auto-tuned motor constant R1, 
1st motor
Units: ohms
H031
Auto-tuned motor constant R2, 
1st motor
Units: ohms
H032
Auto-tuned motor constant L, 
1st motor
Units: mH
H033
Auto-tuned motor constant Io, 
1st motor
Units: A
H034
Auto-tuned motor constant J, 1st 
motor
Units: kgm
2
A003
Base frequency setting
30 to maximum freq.
Units: Hz
A051
DC braking enable
00
Disabled (Disable during auto-
tuning)
01
Enabled
A082
AVR voltage select
200/215/220/230/240
Valid for 200V class inverters
380/400/415/440/
460/480
Valid for 400V class inverters