Setting Motor Constants for Vector Control
Oper
ations
a
nd Moni
tor
ing
4–66
The inverter has three separate motor constant sets named 1st2nd, and 3rd. The 1st motor 
constant set is the default, while the SET and SET2 intelligent inputs select the 2nd and 3rd 
constant sets, respectively. The torque control methods are valid to use only if a particular 
motor constant set includes parameters for the selected control method. The following table 
lists the vector control methods and shows the ones that are valid for each motor constant set.:
The motor data selection is available only to the 1st motor constant set, selected by function 
H004. By default, the 2nd and 3rd motor constants sets only store standard motor parameters. 
The table below shows this arrangement.
When motor constant values are available from the motor manufacturer, you can enter them 
directly. The available motor constant parameters (storage locations) depend on the motor 
constant set (1st, 2nd, or 3rd) according to the following table.
H031
Auto-tuned constant R2, 1st motor
0.000–65.53
Units: ohms
H032
Auto-tuned constant L, 1st motor
0.00–655.3
Units: mH
H033
Auto-tuned constant Io, 1st motor
0.00–655.3
Units: A
H034
Auto-tuned constant J, 1st motor
0.001–9999
Units: kgm
2
Vector Control Method
1st motor
2nd motor
3rd motor
V/f constant torque
V/f variable torque
V/f free-setting curve
Sensorless vector control (SLV)
Sensorless vector control, 0Hz domain
Vector control with encoder feedback
Motor data selection
1st motor
2nd motor
3rd motor
Standard motor parameters
Auto-tuning parameters
Adaptive tuning parameters
Motor data selection
1st motor
2nd motor
3rd motor
Standard motor parameters
H020 to H024
H220 to H224
Auto-tuning parameters
H030 to H034
Adaptive tuning parameters
H030 to H034
Func.
Name
Data
Notes