Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
SJ300 Inverter
T
roub
leshooting
and Maintenance
6–11
Megger Test
The megger is a piece of test equipment that uses a high voltage to determine if an insulation 
degradation has occurred. For inverters, it is important that the power terminals be isolated 
from the Earth GND terminal via the proper amount of insulation.
The circuit diagram below shows the inverter wiring for performing the megger test. Just follow 
the steps to perform the test:
1. Remove power from the inverter and wait at least 5 minutes before proceeding.
2. Open the front housing panel to access the power wiring.
3. Remove all wires to terminals [R, S, T, PD, P, N, RB, U, V, and W]. Most importantly, the 
input power and motor wires will be disconnected from the inverter.
4. Remove the jumper at connector J61. It is located on the main circuit board beside the 
power terminals.
5. Use a bare wire and short terminals [R, S, T, PD, P, N, RB, U, V, and W] together as shown 
in the diagram.
6. Connect the megger to the inverter Earth GND and to the shorted power terminals as shown. 
Then perform the megger test at 500 VDC and verify 5M
Ω or greater resistance.
7. After completing the test, disconnect the megger from the inverter.
8. Reconnect the jumper at connector J61 as before.
9. Reconnect the original wires to terminals [R, S, T, PD, P, N, RB, U, V, and W].
CAUTION: Do not connect the megger to any control circuit terminals such as intelligent I/O, 
analog terminals, etc. Doing so could cause damage to the inverter.
CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has a surge 
protector between the main circuit terminals above and the chassis ground.
U
V
W
Motor
R
S
T
Disconnect 
power source
P
PD
RB
N
J61
SJ300
Disconnect 
motor wires
Earth 
GND
Megger, 500VDC
Add test
jumper wire
Disconnect jumper at 
J61 before performing 
the megger test
L1
L2
L3