Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
Maintenance and Inspection
T
roub
leshooting
and Maintenance
6–12
Spare parts
We recommend that you stock spare parts to reduce down time, including parts listed below:
Capacitor
Life Curve
The DC bus inside the inverter uses a large capacitor as shown in the diagram below. The 
capacitor handles high voltage and current as it smooths the power for use by the inverter. So, 
any degradation of the capacitor will affect the performance of the inverter. The capacitor bank 
in SJ300 series inverters is replaceable. This section will show you how to replace it in the field.
Capacitor life is reduced in higher ambient temperatures, as the graph below demonstrates. Be 
sure to keep the ambient temperature at acceptable levels, and perform maintenance inspections 
on the fan, heat sink, and other components. If the inverter is installed on a cabinet, the ambient 
temperature is the temperature inside the cabinet.
Part description
Symbol
Quantity
Notes
Used
Spare
Cooling fan
FAN
1, 2, 3... (depends 
on model)
1 or 2
Fan unit at top of housing 
in all models
Auxiliary cooling fan
FAN
0 or 1... (depends 
on model)
0 or 1
–150Lxx, –185Lxx, and  
–220Lxx models
Capacitor bank
CB
1
1
All models
Power 
Input
Inverter
L1/R
Motor
L2/S
L3/T
Rectifier
Variable-frequency Drive
Internal DC Bus
+
+
U/T1
V/T2
W/T3
Converter
Ambient
temperature, °C
Years
Capacitor Life Curve
12 hrs / day operation
1
2
3
4
5
6
7
8
9
10
0
20
40
30
50