B–3
Serial Connection 
Diagrams
The serial connector is to the left of the control logic connector as shown below:
Each device requires just two connections for data transmission and reception. Additionally, the 
device at each physical end of the wiring requires a termination resistor. The SJ300 has built-in 
termination resistors that become part of the circuit when you add a jumper as shown.
TIP: Each slave device on the serial network must have a unique node address, set by parame-
ter C072. If this is a new application, we recommend connecting one new device at a time and 
checking the communications after each addition.
SP SN RP SN
Serial
Communications
Connector
Send/receive (+) Positive
Send/receive (–) Negative
Termination resistor (+)
Termination resistor (–)
SP SN RP SN
SJ300
SJ300
SP SN RP SN
SP SN RP SN
SJ300
Termination jumper
Send/receive (+)
Send/receive (–)