SJ300 Inverter
Appendix B
B–5
Communications Protocol
Introduction to 
Command List
The network master sends a frame to initiate 
communications with a slave, as shown in the 
figure to the right. After the set waiting time 
(per parameter C078, the inverter responds.
The following table lists the commands, single-character codes sent to a particular device on 
the network.
NOTE: Use of command 08 – set inverter parameters to default values first requires setting the 
initialization mode parameter B084 to 01 (initializes parameters only) or 02 (initializes param-
eters and clears the trip history).
Command 
Code
Description
User-selectable
00
Forward / Reverse / Stop command
01
Setting of frequency in standard profile
02
Setting of intelligent terminal state
03
Read all monitor data (block read)
04
Read inverter status
05
Read trip history
06
Read a single parameter value
07
Write a single parameter value
08
Set inverter parameters to default values
09
Verifies that the requested setting can be 
written to EEPROM.
0A
Writes a parameter value to EEPROM
0B
Requests the recalculation of internal constant
Host
(master)
wait
time
frame
Inverter
(slave)
frame