SJ300 Inverter
Appendix B
B–15
Command – 08
The 08 command initializes the inverter parameters to the factory default values. First, you 
must set B84 (use command 07) to specify whether you want to clear the trip history at the 
same time. Also, set B85 to specify the country code for the initialization (use command 07).
The frame format of command 08 follows the 
diagram and specification table.
Command – 09
The 09 command verifies whether or not it is 
possible to set a particular parameter in the 
EEPROM. The frame format of command 08 
follows the diagram and specification table.
The receive frame includes an ACK 
(acknowledge) character, followed by a
2-byte data field with the result.
Element
Description
Size
Value
STX
Control code (STart of TeXt)
1 byte
STX (0x02)
Node
Node (station) address of inverter
2 bytes 01 to 32, and FF (broadcast to all 
nodes)
Command
Transmission command
2 bytes 08
BCC
Block check sum code
2 bytes Exclusive OR of Node, 
Command, and Data
[CR]
Control code (carriage return)
1 byte
[CR] (0x0D)
STX Node
Command
BCC [CR]
Frame format
Element
Description
Size
Value
STX
Control code (STart of TeXt)
1 byte
STX (0x02)
Node
Node (station) address of inverter
2 bytes 01 to 32
Command
Transmission command
2 bytes 09
BCC
Block check sum code
2 bytes Exclusive OR of Node, 
Command, and Data
[CR]
Control code (carriage return)
1 byte
[CR] (0x0D)
Element
Description
Size
Value
STX
Control code (STart of TeXt)
1 byte
STX (0x02)
Node
Node (station) address of inverter
2 bytes 01 to 32
ACK
Control code (ACKnowledge)
1 byte
ACK (0x06)
Data
Parameter value
2 bytes 00 = setting not allowed,
01 = setting is allowed
BCC
Block check sum code
2 bytes Exclusive OR of Node, 
Command, and Data
[CR]
Control code (carriage return)
1 byte
[CR] (0x0D)
STX Node
Command
BCC [CR]
Transmit frame format
STX Node
ACK
Data
BCC [CR]
Receive frame format