Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
SJ300 Inverter
In
v
e
rt
er Mounting
and In
stallati
on
2–3
2. Second-level access - First, ensure no 
power source of any kind is connected to 
the inverter. If power has been 
connected, wait five minutes after 
powerdown and verify the Charge Lamp 
indicator is OFF to proceed. Then locate 
the recessed retention screw at the 
bottom of the main front panel. Use a 
small Phillips screwdriver to remove the 
screw. Press the two latch release areas 
near the “SJ300” label as shown, and 
simultaneously slide the lower front 
downward to release for removal.
Notice the large power terminals  at the bottom of the wiring area. The rubber grommets 
below the power terminals are for wire entry/exit to the power source and motor. Never 
operate the inverter with the front panel removed.
The control terminals connect logic or analog signals for control and monitoring of the 
inverter. The nearby alarm relay provides both normally-open and normally-closed logic for 
interface to an external alarm. The alarm circuit may carry hazardous live voltages even 
when the main power to the inverter is OFF. So, never directly touch any terminal or circuit 
component.
WARNING: Be sure to wait five minutes after powerdown and verify the charge lamp indica-
tor is OFF to proceed. Otherwise there is the risk of electric shock.
Press here and slide cover downward 
Retention screw
Wire entry/exit plate
Logic Connector
Power terminals
Charge lamp indicator