Step-by-Step Basic Installation
In
v
e
rt
er Moun
ting
and Install
a
tion
2–20
Step 7: The process of motor selection is beyond the scope of this manual. However, it must be 
a three-phase AC induction motor. It should also come with a chassis ground lug. If the motor 
does not have three power input leads, stop the installation and verify the motor type. Other 
guidelines for wiring the motor include:
• Use an inverter-grade motor for maximum motor life (1600V insulation).
• For standard motors, use an output filter if the wiring between the inverter and motor 
exceeds 10 meters in length.
Simply connect the motor to the terminals 
[U/T1], [V/T2], and [W/T3] indicated on 
the inverter to the right. This is a good time 
to connect the chassis ground lug on the 
drive as well. The motor chassis ground 
must also connect to the same point. Use a 
star ground (single-point) arrangement, and 
never daisy-chain the grounds (point-to-
point).
Use the same wire gauge on the motor and 
chassis ground wiring as you used on the 
power input wiring in the previous step. 
After completing the wiring:
• Check the mechanical integrity of each 
wire crimp and terminal connection.
• Replace the front panel and secure the 
retention screw firmly.
Logic Control 
Wiring
After completing the initial installation and powerup test in this chapter, you may need to wire 
the logic signal connector for your application. For new inverter users/applications, we highly 
recommend that you first complete the powerup test in this chapter without adding any logic 
control wiring. Then you will be ready to set the required parameters for logic control as 
covered in Chapter 4, Operations and Monitoring.
Step 8: After mounting and wiring the inverter, 
remove any protective material covering the 
inverter ventilation openings from Step 3. This 
includes covers over the side ventilation ports 
as well as the fan outlet area.
CAUTION: Failure to remove all vent opening 
covers before electrical operation may result in 
damage to the inverter.
7
Wire the Inverter 
Output to Motor
To Power 
Source
To Motor
To Chassis 
Ground
8
Uncover the 
Inverter Vents
Uncover the ventilation slots,
both sides