Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
Powerup Test
In
v
e
rt
er Moun
ting
and Install
a
tion
2–22
CAUTION: If you operate a motor at a frequency higher than the inverter standard default 
setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective 
manufacturer. Only operate the motor at elevated frequencies after getting their approval. 
Otherwise, there is the danger of equipment damage and/or injury to personnel.
CAUTION: Check the following before and during the powerup test. Otherwise, there is the 
danger of equipment damage.
Is the shorting bar between the [P] and [PD] terminals installed? DO NOT power or 
operate the inverter if the jumper is removed.
Is the direction of the motor rotation correct?
Did the inverter trip during acceleration or deceleration?
Were the rpm and frequency meter readings as expected?
Were there any abnormal motor vibrations or noise?
Powering the 
Inverter
If you have followed all the steps, cautions and warnings up to this point, you’re ready to apply 
power. After doing so, the following events should occur:
• The POWER LED will illuminate.
• The numeric (7-segment) LEDs will display a test pattern, then stop at 
0.0
.
• The Hz LED will be ON.
If the motor starts running unexpectedly or any other problem occurs, press the STOP key. Only 
if necessary should you remove power to the inverter as a remedy.
NOTE: If the inverter has been previously powered and programmed, the LEDs (other than the 
POWER LED) may illuminate differently than as indicated above. If necessary, you can initial-
ize all parameters to the factory default settings. See 
.