Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
“F” Group: Main Profile Parameters
Configur
ing Dr
iv
P
a
ra
meters
3–8
“F” Group: Main Profile Parameters
The basic frequency (speed) profile is 
defined by parameters contained in the 
“F” Group as shown to the right. The 
output frequency is set in Hz, but accel-
eration and deceleration are specified 
seconds (the time to ramp from zero to 
maximum frequency, or from maximum 
frequency to zero). The motor direction 
parameter determines whether the 
keypad Run key produces a FW or RV 
command. This parameter does not 
affect the [FW] terminal or [RV] intelligent terminal function, which you configure separately.
Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the main 
profile. Accel and decel values for an alternative profile are specified by using parameters Ax92 
through Ax93. The motor direction selection (F004) determines the direction of rotation as 
commanded only from the keypad. This setting applies to any motor profile (1st, 2nd, or 3rd) in 
use at a particular time.
Output
frequency
F001
F002
F003
t
“F” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
F001
Output frequency 
setting
Standard default target 
frequency that determines 
constant motor speed
Range is 0 to 400 Hz
✔ ✔ 0.00 0.00 0.00
Hz
>F001 SET-Freq.
TM     0000.00Hz
2FS    0000.00Hz
3FS    0000.00Hz
TM     0000.00Hz
JG     0000.00Hz
1S     0000.00Hz
15S    0000.00Hz
OP1    0000.00Hz
OP2    0000.00Hz
RS485  0000.00Hz
F002
Acceleration (1) time 
setting
Standard default accelera-
tion
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0
sec.
>F002 ACCEL
TIME1   0030.00s
F202
Acceleration (1) time 
setting, 2nd motor
Standard default accelera-
tion, 2nd motor
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0
sec.
>F202 2ACCEL
TIME1   0030.00s
F302
Acceleration (1) time 
setting, 3rd motor
Standard default accelera-
tion, 3rd motor
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0
sec.
>F302 3ACCEL
TIME1   0030.00s
F003
Deceleration (1) time 
setting
Standard default decelera-
tion
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0
sec.
>F003 DECEL
TIME1   0030.00s
F203
Deceleration (1) time 
setting, 2nd motor
Standard default decelera-
tion, 2nd motor
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0
sec.
>F203 2DECEL
TIME1   0030.00s
F303
Deceleration (1) time 
setting, 3rd motor
Standard default decelera-
tion, 3rd motor
Range is 0.01 to 3600 sec.
✔ ✔ 30.0 30.0 30.0
sec.
>F303 3DECEL
TIME1   0030.00s
F004
Keypad Run key routing Two options; select codes:
00 Forward
01 Reverse
✘ ✘
00
00
00
>F004 DIG-RUN
SELECT        FW