Automatic 
Voltage
Regulation (AVR) 
Function
The automatic voltage regulation (AVR) feature keeps the inverter output voltage at a 
relatively constant amplitude during power input fluctuations. This can be useful if the installa-
tion is subject to input voltage disturbances. However, the inverter cannot boost its motor 
output to a voltage higher than the power input voltage. If you enable this feature, be sure to 
select the proper voltage class setting for your motor.
Energy Savings 
Mode / Optimal 
Accel/Decel
Energy Savings Mode – This function allows the inverter to deliver the minimum power 
necessary to maintain speed at any given frequency. This works best when driving variable 
torque characteristic loads such as fans and pumps. Parameter A085=01 enables this function 
and A086 controls the degree of its effect. A setting of 0.0 yields slow response but high 
accuracy, while a setting of 100 will yield a fast response with lower accuracy.
Optimal Accel/Decel Operation – This feature uses “fuzzy” logic to optimize acceleration 
and deceleration curves in real time. It is enabled by A085=02. Optimal accel/decel operation 
automatically adjusts the acceleration and deceleration times in response to changes in load or 
inertia to take advantage of the maximum output current capability of the inverter. In general, 
optimal accel/decel will allow for the shortest accel and decel times based on the actual load 
conditions. The function continuously monitors output current and DC bus voltage to avoid 
reaching their respective trip levels.
NOTE: In this mode, the settings of acceleration and deceleration times (F002 and F003) are 
disregarded.
“A” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
A081 AVR function select
Automatic (output) voltage 
regulation, selects from 
three type of AVR functions, 
three option codes:
00 AVR enabled
01 AVR disabled
02 AVR enabled except 
during deceleration
✘ ✘
00
00
00
>A081 AVR
MODE        DOFF
A082 AVR voltage select
200V class inverter settings:
200/215/220/230/240
400V class inverter settings:
380/400/415/440/460/
480
✘ ✘
230/
400
230/
460
200/
400
V
>A082 AVR
AC          230
“A” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
A085 Operation mode
selection
Three options:
00 Normal operation
01 Energy-saver operation
02 Optimal accel/decel 
operation 
✘ ✘
00
00
00
>A085 RUN
MODE       NOR
A086 Energy saving mode 
tuning
Range is 0.0 to 100 sec.
✔ ✔ 50.0 50.0 50.0
sec.
>A086 RUN
ECO      0050.0s