Hitachi SJ300-037HFE 사용자 설명서

다운로드
페이지 289
“A” Group: Standard Functions
Configur
ing Dr
iv
P
a
ra
meters
3–26
Accel/Decel 
Characteristics
Standard (default) acceleration and deceleration is linear with time. The inverter CPU can also 
calculate other curves shown in the graphs below. The sigmoid, U-shape, and reverse U-shape 
curves are useful for favoring the load characteristics in particular applications. Curve settings 
for acceleration and deceleration are independently selected via parameters A097 and A098, 
respectively. You can use the same or different curve types for acceleration and deceleration.
time
Output frequency
time
Output frequency
time
Output frequency
time
Output frequency
time
Output frequency
time
Output frequency
time
Output frequency
time
Output frequency
Linear
Sigmoid
U-shape
Reverse U-shape
Accel
A97
Decel
A98
00
Set value
Curve
01
02
03
Linear acceleration 
and deceleration for 
general-purpose use
Avoid jerk on start/stop 
for elevators; use for 
delicate loads on con-
veyors
Tension control for winding applications, web 
presses, roller/accumulators
Typical
applications
“A” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
A097 Acceleration curve 
selection
Set the characteristic curve 
of Accel1 and Accel2, four 
options:
00 Linear
01 S-curve
02 U-shape
03 Reverse U-shape
✘ ✘
00
00
00
>A097 ACCEL
LINE  Linear
A098 Deceleration curve 
selection
Set the characteristic curve 
of Decel1 and Decel2, four 
options:
00 Linear
01 S-curve
02 U-shape
03 Reverse U-shape
✘ ✘
00
00
00
>A098 DECEL
LINE  Linear