“A” Group: Standard Functions
Configur
ing Dr
iv
P
a
ra
meters
3–28
Additional 
Analog Input 
Settings
The parameters in the following table adjust the input characteristics of the analog inputs. 
When using the inputs to command the inverter output frequency, these parameters adjust the 
starting and ending ranges for the voltage or current, as well as the output frequency range. 
Related characteristic diagrams are located in 
.
“A” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
A101 [OI]–[L] input active 
range start frequency
The output frequency corre-
sponding to the current input 
range starting point.
Range is 0.00 to 400.0 Hz
✘ ✔ 00.0 00.0 00.0
Hz
>A101 INPUT-OI
EXS    0000.00Hz
A102 [OI]–[L] input active 
range end frequency
The output frequency corre-
sponding to the current input 
range ending point.
Range is 0.00 to 400.0 Hz
✘ ✔ 00.0 00.0 00.0
Hz
>A102 INPUT-OI
EXE    0000.00Hz
A103 [OI]–[L] input active 
range start current
The starting point for the 
current input range.
Range is 0 to 100%
✘ ✔
20.
20.
20.
%
>A103 INPUT-OI
EX%S        020%
A104 [OI]–[L] input active 
range end current
The ending point for the 
current input range.
Range is 0 to 100%
✘ ✔ 100. 100. 100.
%
>A104 INPUT-OI
EX%E        100%
A105 [OI]–[L] input start 
frequency enable
Two options:
00 Use A101 start value
01 Use 0Hz
✘ ✔
01
01
01
Hz
>A105 INPUT-OI
LEVEL     0Hz
A111 [O2]–[L] input active 
range start frequency
The output frequency corre-
sponding to the bipolar 
voltage input range starting 
point.
Range is –400. to 400. Hz
✘ ✔ 0.00 0.00 0.00
Hz
>A111 INPUT-O2
EXS    +000.00Hz
A112 [O2]–[L] input active 
range end frequency
The output frequency corre-
sponding to the bipolar 
voltage input range ending 
point.
Range is –400. to 400. Hz
✘ ✔ 0.00 0.00 0.00
Hz
>A112 INPUT-O2
EXE    +000.00Hz
A113 [O2]–[L] input active 
range start voltage
The starting point for the 
bipolar voltage input range. 
Range is –100 to 100%
✘ ✔ -100. -100. -100.
%
>A113 INPUT-O2
EX%S       -100%
A114 [O2]–[L] input active 
range end voltage
The ending point for the 
bipolar voltage input range. 
Range is –100 to 100%
✘ ✔ 100. 100. 100.
%
>A114 INPUT-O2
EX%E       +100%