Multi-Speed Select ~Binary Operation 
The inverter can store up to 16 different target 
frequencies (speeds) that the motor output uses for 
steady-state run condition. These speeds are accessible 
through programming four of the intelligent terminals as 
binary-encoded inputs CF1 to CF4 per the table to the 
right. These can be any of the six inputs, and in any 
order. You can use fewer inputs if you need eight or 
fewer speeds. 
 
NOTE: When choosing a subset of speeds to use, 
always start at the top of the table, and with the 
least-significant bit: CF1, CF2, etc. 
 
 
 
 
 
The example with eight speeds in the 
figure below shows how input switches 
configured for CF1–CF3 functions can 
change the motor speed in real time. 
 
NOTE: Speed 0 depends on 
A001
 
parameter value. 
 
 
Option 
Code 
Terminal 
Symbol 
Function Name 
State
Description 
ON 
Binary encoded speed select, Bit 0, logical 1 
02 
CF1 Multi-speed 
Select, 
Bit 0 (LSB) 
OFF
Binary encoded speed select, Bit 0, logical 0 
ON 
Binary encoded speed select, Bit 1, logical 1 
03 
CF2 Multi-speed 
Select, 
Bit 1 
OFF
Binary encoded speed select, Bit 1, logical 0 
ON 
Binary encoded speed select, Bit 2, logical 1 
04 
CF3 Multi-speed 
Select, 
Bit 2 
OFF
Binary encoded speed select, Bit 2, logical 0 
ON 
Binary encoded speed select, Bit 3, logical 1 
05 
CF4 Multi-speed 
Select, 
Bit 3 (MSB) 
OFF
Binary encoded speed select, Bit 3, logical 0 
Valid for inputs: 
C001
~
C007
 
Required settings 
F001
A001
=
02
A020
 to 
A035
 
Notes: 
•  When programming the multi-speed settings, be 
sure to press the SET key each time and then set 
the next multi-speed setting. Note that when the 
key is not pressed, no data will be set. 
•  When a multi-speed setting more than 50Hz 
(60Hz) is to be set, it is necessary to program the 
maximum frequency 
A004
 high enough to allow 
that speed 
Example (some CF inputs require input 
configuration; some are default inputs): 
 
 
 
 
 
 
 
 
 
See I/O specs on 
page 21,22.
 
 
Multi- 
speed 
Input Function 
 CF4 
CF3 
CF2 
CF1 
Speed 0
Speed 1
Speed 2
Speed 3
Speed 4
Speed 5
Speed 6
Speed 7
Speed 8
Speed 9
Speed 10
Speed 11
Speed 12
Speed 13
Speed 14
Speed 15
 
Speed 
0th
4th
6th
1st
2nd
5th
7th
3rd
1
0
1
0
1
0
1
0
[CF1] 
[CF2] 
[CF3] 
[FW] 
CF4 CF3 CF2 CF1
 
7
6
5
4
3
2
1
 
L
 
P24
 
PLC